310_729_001_1111.fm Seite 11 Freitag, 2. Dezember 2011 11:58 11
Installation position
Connection L1, N
Protective conductor
connection
Special seal
Cable entry
Approval
6.2
Minimum gap length
Minimum gap
Between upper and lower sections of
length
the housing
Between lower section of housing and
conductor bushing
6.3
Explosion protection
729
785
6.4
Electrical Data
Type
Voltage
729 x00 55
24 V=
729 x00 68
230 V~
785 x00 75
24 V
785 x00 70
115...230 V 0/50/60 Hz 24 V
x = color
1 = red
3 = yellow
7
Mounting
For dimensions and mounting see "Zeichnungen / Drawings / Dessins" page 20.
If required, a wire guard can be screwed on (accessory).
7.1
Opening of the Ex d housing
Caution
• Do not open the light fitting under a live voltage!
• After disconnecting the power, observe the prescribed waiting time before
opening it.
• Power is only to be switched on when the housing is closed and it has been
ensured that all explosion protection measures have been taken.
Unscrew the M5 set screw.
as required
0.5 ... 2.5 mm² single, fine and multi-wire
(stripped length 8-9 mm)
inside: 0.5 ... 2.5 mm² single, fine and multi-wire
Ready-for-use / unassembled
outside: 4 mm², max. torque 2 Nm
Ex d case thread M130*2, secured with M4 hexagon socket
set screw DIN 914
1 x M20 x 1.5 Ex-screwed cable glands
1 x M20 x 1.5 Ex-vent plug, Ex-Metal cable entry possible
Follow the installation manual of the cable glands!
BVS 11 ATEX 107
IECE
_BVS_11.0082, www.iecex.com
x
II2G Ex d e IIC T6 Gb -50 °C ... +50 °C
II2D Ex tb IIIC T80 °C Db -50 °C ... +50 °C IP 66
II2G Ex d e IIC T6/T5 Gb -50 °C ... +50 °C
II2D Ex tb IIIC T95 °C Db -50 °C ... +50 °C IP 66
Frequency
Lamp
Current
consumption
LED
130 mA
50/60 Hz
LED
30 mA
0/50/60 Hz 12 V
20 W
350 mA (115V~)
20 W
150 mA (230V~)
8 mm / 5 thread turns
12 mm / 8 thread turns
Loop
Power
through
consump
current
tion.
16 A
3 W
16 A
1.3 W
1 A
16 A
22 W
16 A
22 W
T
Surface
class
temp.
T6
80 °C
T6
80 °C
T5
95 °C
T5
95 °C
11