1. Safety instructions
a
• For skilled electricians and trained
personnel in accordance with national
legislation, including the relevant standards
and, where applicable, in acc. with
IEC/EN 60079-17 on electrical apparatus for
explosive atmospheres.
• The battery must not be operated in Zone 0
or zone 20 hazardous areas!
• The technical data indicated on the battery
is to be observed!
• Changes or modifications to the battery are
not permitted!
• The battery is only to be used as intended
and in undamaged and correct working
order!
• Only genuine Eaton's Crouse-Hinds Business
(Eaton)/CEAG parts are to be used!
• Repairs that affect the protection against
explosion, may only be performed by
Eaton's Crouse-Hinds Business (Eaton)/
CEAG or a qualified electrician (see relevant
national regulations)!
• Observe the national health and safety
regulations for prevention of accidents that
are marked with a (
) in these operating
instructions!
Operation and fault indicator
Green LED
Red LED
V
V
,
,
,
V
v
V
v
V
V
Important information relating to occurrence of a lamp fault:
0
Under certain conditions (e.g. low temperature range) a supposed lamp fault (red LED flashing) can possibly be eliminated and
replacement of the lamp avoided. Initiate a manual mains failure. This causes the emergency lighting function to start up.
After ca. 1 minute the fault is eliminated. If, however, the red LED continues to flash, it is necessary to replace the lamp .
2.
Technical data
ATEX type examination certificate:
eBK 12 NE / eBS 12 NE/ eBB 12 NE:
Marking acc. to 94/9/EC and standard EN 60079-0:
IECEx type examination certificate:
Category of application acc. to IEC60079-0:
Battery
NE 2710-12
Operation and fault indicator:
Rated capacity:
Charging time:
Operation temperature
in combination with lamp fitting eLL.:
Specified data kept at temperature:
Storage temperature in original packing
less then 1 Month
Insulation class:
Cable glands certified
acc. 94/9/EG
Weight
:
1) Note: New batteries will reach their total useful capacity only after 3 charging/discharging cycles.
Further technical data can be found in the Operating Instructions
eLLK 92 NE/ eLLS 08 NE (300 8000 1460) or eLLB 20 NE (300 8000 2238)
Meaning
Continuous green light
g Faultfree state/battery is charged, or emergency lighting mode
Flashing green light
g Battery charging, function test or continuous operation test
Green and red LEDs flash alternately
g Cycle test
Green and red LEDs flash simultaneously
g Battery charging and lamp fault
Flashing red light
g Detection of lamp fault in emergency lighting mode
Flashiing green light and continuous red light
g Battery charged, but battery fault detected
Continuous red light
g Battery faullt, emergency lighting duration less than 60 mins.
Both LEDs are off
g No mains and battery empty or not connected
V
LED red/green off
Battery set: NE 2710-12:
eBK 12 NE/ eBS 12 NE/ eBB 12 NE:
Battery set: NE 2710-12:
eBK 12 NE/ eBS 12 NE / eBB 12 NE:
Battery set: NE 2710-12:
eBK 12 NE/ eBS 12 NE/ eBB 12 NE:
Battery set: NE 2710-12:
:
:
IEC/EN 61140:
v red
green on
LED
EATON'S CROUSE-HINDS BUSINESS
BVS 09 ATEX E044 X
BVS 09 ATEX E042 U
Ex d e mb ib IIC T4 Gb
II 2 G
Ex tb IIIC T80°C Db
II 2 D
Ex d e mb ib IIC Gb
II 2 G
IECEx BVS 11.0003X
IECEx BVS 14.0085U
Ex d e mb ib IIC T4 Gb
Ex tb IIIC T80°C Db
Ex d e mb ib IIC Gb
5 x NC-
accumulators
BVS ATEX E 103 U / D II 2 G Ex e IIC Gb
IECEx BVS 11.0073 U / Ex e IIC Gb
1x green LED
1x red LED
1)
7 Ah
approx. 14 h (>90%)
-25°C
to +55°C
-5°C
to +40°C
+5°C
to
+35°C
-40°C
to
+65°C
III
2 x M25 x 1,5 or
2 x connector system CEAG GHG 57 (eXLink)
approx.
5,2 kg
Action
none
none
none
Lamp replacement followed* by
testing of emergency lighting mode
Lamp replacement followed* by
testing of emergency lighting mode
Battery replacement
Battery replacement
Check mains/supply voltage
,
red
LED
green flashing