D
®
RHEASGARD
KLGF-Modbus ⁄ KLGFVT-Modbus | Telegramme
TELEGRAMME
Function 04 Read Input Register
Register
Parameter
0003
Flow
0004
Flow
0006
Temperatur
0007
Temperatur
0008
Volumenstrom
0009
Volumenstrom
0010
Volumenstrom
Function 06 Write Single Register &
Function 16 Write Multiple Register
Register
Parameter
0001
Displaydarstellung
0002
Einheit Volumenstrom
0004
digitaler Offset Strömung
0007
digitaler Offset Temperatur
0009
Kanalquerschnitt in cm²
0015
Nullpunkt setzen (0 m/s)
Abtastung 4 s
Signed 16 Bit
Filterung max. 32 s
Signed 16 Bit
Abtastung 4 s
Signed 16 Bit
Filterung max. 32 s
Signed 16 Bit
Abtastung 4 s
Signed 16 Bit
Filterung max. 32 s
Signed 16 Bit
Einheit
Signed 16 Bit
Data Type
Value
Signed 16 Bit
0...5
Signed 16 Bit
0...5
Signed 16 Bit
–50...50
Signed 16 Bit
–50...50
Signed 16 Bit
10...30000
Signed 16 Bit
0...1
7
Data Type
Value
0...200
0...200
0...500
0...500
0...30000
0...30000
0...5
default
KLGF
0
0 = Strömung
KLGFVT 5
1 = Strömung + Temperatur
2 = Volumenstrom
3 = Volumenstrom + Temperatur
4 = Volumenstrom + Strömung
5 = Volumenstrom / Strömung
altern. + Temperatur
0
0 = m³ ⁄ h
1 = m³ ⁄ min
2 = m³ ⁄ s
3 = l ⁄ h
4 = l ⁄ min
5 = l ⁄ s
0
–5.0...5.0 m ⁄ s
0
–5.0...5.0 °C
10000
10 cm²...30000 cm²
0
0 = inaktiv
1 = setzen / aktivieren
(anschießend springt der Wert
automatisch wieder auf 0)
Range
0.0...20.0 m ⁄s
0.0...20.0 m ⁄s
0.0...50.0 °C
0.0...50.0 °C
0...30000
0...30000
0 = m³ ⁄ h
1 = m³ ⁄ min
2 = m³ ⁄ s
3 = l ⁄ h
4 = l ⁄ min
5 = l ⁄ s