4.2 Connection of electronically regulated circulating pumps

Electronically regulated circulating pumps have high starting
currents, which may shorten the service life of the heat pump
manager. For this reason, a coupling relay is installed or must be
installed between the output of the heat pump manager and the
electronically regulated circulating pump. This is not necessary if
the permissible operating current of 2 A and a maximum starting
current of 12 A are not exceeded in the electronically regulated
F2
Load fuse for plug-in terminals J12, J13
and J21 5x20 / 4.0 AT
F3
Load fuse for plug-in terminals J15 to J18
and J22 5x20 / 4.0 AT
N1
Control unit
T1
Safety transformer 230/24 V AC
X1
Terminal strip - infeed
X2
Terminal strip, voltage = 230 V AC
X3
Terminal strip, extra-low voltage < 25 V AC
X11 Module connection plug
X12 Connecting cable plug
Heat pump controller - 230 V AC
X13.1Connecting cable plug
Heat pump controller - < 25 V AC
X13.2Connecting cable plug
Heat pump controller - < 25 V AC
NOTE
Detailed circuit diagrams can be found in the Appendix, chapter 3
NOTE
Two or three connection cables must be laid between Econ5 
(< 25 V; = 230 V; communication cable IT).
circulating pump or if express approval has been issued by the
pump manufacturer.
ATTENTION!
It is not permitted to connect more than one electronically regulated
circulating pump via a relay output.
452114.66.98 FD 9310
WPM Econ5Plus - WPM Econ5R
EN-7