Current monitoring relay
EIW-C18
24 V AC
11027210
230 V AC
11027205
1. Description
The EIW-C18 serves as monitor for direct or alternating currents
in voltage power stations. It indicates an overrun or underrun of
the selected thresholds and releases a switching operation. In case
of an error the numeric displays indicate the cause of error. Ma-
nual settings on the device allow to select the current type to be
measured (AC or DC), one measuring range out of two (0.01 A to
1 A or 1 A to 15 A), an upper and a lower threshold, the response
delay (0.1 s to 9.9 s) and the error memory (on or off).
The two current measuring ranges (0.01 A to 1 A or 0.1 A to 15 A)
are selected by the contacts.
Errors can be acknowledged directly on the device and via an
external contact.
METZ CONNECT GmbH | Im Tal 2 | 78176 Blumberg | Germany
Phone +49 7702 533-0 | Fax +49 7702 533-433
Weitere Dokumentation siehe / additional documentation see / documentation supplémentaire voir www.metz-connect.com
2. Declaration of Conformity
The device was tested according to the applicable standards.
Conformity was proofed. The declaration of conformity is available
at the manufacturer BTR NETCOM GmbH.
Notes Regarding Device Description
These instructions include indications for use and mounting of the
device. In case of questions that cannot be answered with these
instructions please consult supplier or manufacturer.
The indicated installation directions or rules are applicable to the
Federal Republic of Germany. If the device is used in other coun-
tries it applies to the equipment installer or the user to meet the
national directions.
Safety Instructions
Keep the applicable directions for industrial safety and prevention
of accidents as well as the VDE rules.
Technicians and/or installers are informed that they have to
electrically discharge themselves as prescribed before installation
or maintenance of the devices.
Only qualified personnel shall do mounting and installation work
with the devices, see section "qualified personnel".
The information of these instructions have to be read and
understood by every person using this device.
Symbols
Warning of dangerous electrical voltage
Danger
means that non-observance may cause risk of life,
grievous bodily harm or heavy material damage.
Qualified Personnel
Qualified personnel in the sense of these instructions are persons
who are well versed in the use and installation of such devices
and whose professional qualification meets the requirements of
their work.
This includes for example:
Qualification to connect the device according to the
l
VDE specifications and the local regulations and a qualification
to put this device into operation, to power it down or to activate
it by respecting the internal directions.
Knowledge of safety rules.
l
Knowledge about application and use of the device within the
l
equipment system etc.
3. Technical Data
Supply
Operating Voltage U
24 V AC
B
230 V AC / 50 Hz
Power consumption at U
AC max. 15 mA
B
Operating voltage range
0.9 ... 1.1 x U
B
Duty cycle
100 %
Measuring circuit
Voltage measuring inputs
B1 - B3
0.01 A ... 1 A
B2 - B3
0.1 A ... 15 A
Response delay
selectable 0.1 ... 9.9 s
Switching hysteresis
selectable 1 - 30 %
Measuring frequency
100 ms
Temperature error
≤0.06 % / °C
Measuring error within U
≤12 %
B
Ambient temperature
-10 °C ... +55 °C
Output
Output contact
2 changeover contacts
Contact material
AgNi
Switching voltage max.
250 V AC/DC
Nominal current max.
8 A
Making/breaking capacity
230 V~ 6 A AC1
230 V~ 3 A AC3
Load limit curve
for direct current
Contact fuse
6 A
6
Mechanical endurance
30 x 10
switching cycles
5
Electrical endurance
1 x 10
switching cycles
Test voltage coil/contact
2 kV 50 Hz 1 min.
Housing
Dimensions WxHxD
50 x 68 x 65 mm
Weight
200 g
Mounting position
any
Mounting
standard rail TH35 per IEC 60715
Material
Housing
Polyamide 6.6 V0
Terminal blocks
Polyamide 6.6 V0
Cover plate
Polycarbonate
Type of protection
(EN 60 529)
Housing
IP40
Terminal blocks
IP20
Terminal blocks
Relay connection
Input/Output
max. 4 mm² solid wire
max. 2.5 mm² stranded wire
with end sleeve
Temperature range
Operation
-5 °C ... +55 °C
Storage
-20 °C ... +70 °C
Display
Function
green LED
Error indication
2 x 7-segment-display
Error signal
red LED
4. Connection diagram
Note
S1, S2 are non-isolated against the measuring circuit B1, B2
and B3! In measurements of direct current (DC) the polarity
has to be respected!
Measuring range: b1:
B1(+), B3(-)
b2:
B2(+), B3(-)
5. Mounting
Power down the equipment
Mount the module on standard rail (TH35 per IEC 60715 in
junction boxes and/or on distribution panels).
Installation
Electric installation and device termination shall be done by
qualified persons only, by respecting all applicable
specifications and regulations.
1
2
3
4
7 mm
Strip the wire by 7 mm, put on an end sleeve, insert the wire to
the contact and fasten it with a screwdriver.