5.1
Compressed air supply condition
a.
Dry air with a temperature at least 10°C below the ambient temperature.
b.
Avoid dusty air. The filter can only screen out particles 5 microns or larger.
c.
Avoid any oil contamination.
d.
Be sure to observe the pressure equipment guideline.
e.
Do not set the regulator beyond 1.4 – 6 bar.
f.
Set the supply pressure on the air filter regulator 10% higher than the controlled range of the pneumatic drive.
5.2
Air line condition
4.
Be sure the line is empty.
5.
Never use kinked or ruptured tubes or pipes.
6.
Use
a
5.3
Connecting the pipe to the drive
On a single-acting SR 1000 L use the output OUT1. When using a one-way drive where the springs set the initial state, connect output
OUT1 with the drive.
6
Attitudes for ,,Spring opens''
,,Spring closes'' is according to standard. For ,,spring opens'' the compressed air supply must be connected with the upper cover (see figure 11).
line
with
an
inside
diameter
Figure 10- spring closes
Figure 11-spring opens
6139-8010
greater
than
4
mm
to
ensure
the
proper
flow
rate
07/2018