Oilbuner
Type Gulliver RG0.R
Combustion adjustment:
To suit the required appliance output, fit the nozzle then adjust the pump pressure, and the
air damper opening in accordance with the following schedule.
Nozzles recommended:
Delavan:
Danfoss:
Monarch:
Steinen:
Nozzle
[GPH]
0,40
0,50
0,60
Nozzle and pump pressure on highest capacity:
Nozzle
[GPH]
0,60
0,65
0,75
If the oil burner has to run in the highest ca-
pacity the diffuser disc has to be changed
(see page 6) and the enclosed sticker is to
be put on the model sign.
K:\framen\instrukt\Dantherm\RG\Engelsk\RG0r\RG0R.fm-I2-020916-dm/lbk
Adjustment
Type W – B
Type S – B
Type R
Type S – Q
Pump pressure
angle
[bar]
60°
11
60°
12
60°
12
Pump pressure
angle
[bar]
60°
12
60°
12
60°
13
Burner output
[kg/h ± 4%]
1,4
1,9
2,3
Burner output
[kg/h ± 4%]
2,3
2,5
3,0*
*At maximum capacity the isolation (3,
page 4) has to be removed in order to incre-
ase the air capacity.
GB
Air damper
adjustment
1,0
1,8
2,8
Air damper
adjustment
2,2
2,7
3,9
page 7 of 10