Penn | TC3B22 | Installation Guide Rev. A | Part No. 24-7664-03868 | Page 1 of 14 | January 20, 2022
TC3B22
Basic Defrost Controller European Installation Guide
Basic controller for refrigerated cabinets, with energy-saving strategies
Figure 1: UI
Figure 2: Dimensions, mm (in.)
Figure 3: Drilling template, mm (in.)
Figure 4: Electrical connection
ENGLISH
-
Controller for normal and low temperature units
-
Power supply for TC3B22N7x: 230 VAC
-
Cabinet probe and auxiliary probe with a negative temperature coefficient (NTC)
-
Door switch or multi-purpose input
-
Cooling or heating operation
1
MEASUREMENTS AND INSTALLATION
For the dimensions and drilling template, see Figure 2 and Figure 3. Fit the controller to a panel
with the snap-in brackets supplied.
INSTALLATION PRECAUTIONS
-
Ensure that the thickness of the panel is between 0.8 mm and 2.0 mm (1/32 and 1/16
in)
-
Ensure that the working conditions are within the limits stated in TECHNICAL
SPECIFICATIONS.
-
Do not install the device close to heat sources, equipment with a strong magnetic field,
in places subject to direct sunlight, rain, damp, excessive dust, mechanical vibrations or
shocks.
-
In compliance with safety regulations, install the device correctly to ensure adequate
protection from contact with electrical parts. Fix all protective parts in such a way so as
to need the aid of a tool to remove them.
2
ELECTRICAL CONNECTION
Important
- Use cables of an adequate wire gauge for the current running through them.
- To reduce any electromagnetic interference, connect the power cables as far away
as possible from the signal cables.
For the electrical connection diagram, see Figure 4.
Electrical connection diagram callouts
Callout
Description
A
Note: Maximum 10 A
B
Compressor
C
Evaporator fans, configurable
D
Door switch or multi-purpose
E
Cabinet
F
Auxiliary, configurable
G
Power supply for TC3B22N7x: 230 VAC
PRECAUTIONS FOR ELECTRICAL CONNECTION
If you use an electrical or pneumatic screwdriver, adjust the torque to a maximum of
-
0.5 N•m (4 in. lb).
If you move the device from a cold to a warm place, the humidity may cause
-
condensation to form inside. Wait an hour before you switch on the power.
Make sure that the supply voltage, electrical frequency, and power are within the set
-
limits. See TECHNICAL SPECIFICATIONS.
Disconnect the power supply before you do any type of maintenance.
-
Do not use the device as safety device.
-
For repairs and further information, contact the Penn sales network.
-
3
FIRST-TIME
1.
Follow the instructions in MEASUREMENTS AND INSTALLATION to install the controller.
2.
Power up the device as shown in ELECTRICAL CONNECTION and an internal test runs.
The test normally takes a few seconds. When it finishes the display switches off.
3.
Configure the device as shown in Table 6.1 in SETTINGS.
For recommended configuration parameters for first-time use, see the following table.
PAR.
DEF.
PARAMETER
MIN. - MAX.
SP
Setpoint
r1 to r2
0.0
P2
0
Temperature unit of measurement
0 = °C
d1
0
Defrost type
0 = Electric
2 = Compressor stopped
Check that the remaining settings are appropriate; see CONFIGURATION PARAMETERS.
4.
Disconnect the device from the mains.
5.
Make the electrical connection as shown in ELECTRICAL CONNECTION without powering
up the device.
6.
Power up the device.
4
UI AND MAIN FUNCTIONS
For a figure of the UI, see Figure 1.
UI callouts
Callout
Description
1
Energy saving
2
n/a
3
Temperature unit of measurement
4
Compressor
5
Defrost
6
Evaporator fan
7
n/a
8
Auxiliary
9
On or standby
10
SET key and keypad lock
11
ON/STANDBY key, escape, and cabinet light
12
DOWN key and additional functions menu
13
UP key and defrost
4.1
Switching the device on or off
1.
If POF = 1, tap the ON/STAND-BY key for 4 s.
If the device is switched on, the display shows the P5 value, cabinet temperature by default. If
the display shows an alarm code, see ALARMS.
LED
ON
Compressor on
Defrost or pre-dripping
active
Evaporator fan on
AUX
- Alarm active
- Cabinet light on by
key
- If device on, energy
saving active
- If device off, low
consumption active
°C/°F View temperature
Device off
If 30 s have elapse and you do not press the keys, the display shows the "Loc" label and the
keypad locks automatically.
4.2
Unlocking the keypad
Tap any key for 1 s. The display shows the label "UnL".
4.3
Setting the setpoint
Check that the keypad is not locked.
1.
Tap the SET key.
2.
Tap the UP or DOWN key within 15 s to set the value within the
limits r1 and r2.
3.
Tap the SET key or do not operate for 15 s.
4.4
Activating manual defrost (if r5 = 0, default)
Check that the keypad is not locked.
1.
Tap the UP key for 2 s.
If P4 = 1 (default), the defrost activates if the evaporator temperature is lower than the d2
threshold.
4.5
Turning the cabinet light on or off (if u0 = 3)
1.
Tap the ON/STAND-BY key.
5
ADDITIONAL FUNCTIONS
5.1
Navigating the additional functions menu
Before you begin, check that the keypad is not locked.
1.
To access the additional functions menu, tap the DOWN key for
4 s.
2.
To navigate to a label, tap the UP or DOWN key within 15 s.
3.
To select a label, tap the SET key.
4.
If you cannot edit the parameter, the value displays.
If you can edit the parameter, tap the UP or DOWN key to
navigate to the value that you want.
5.
To set the parameter value, tap the SET key.
6.
To exit the procedure, tap the ON/STAND-BY key, or do not
operate the controller for 60 s.
5.2
Additional functions menu
Use the additional functions menu to cycle through the labels in the following table.
LABEL
VALUE
DESCRIPTION
CH
View compressor functioning hours in hundreds
rCH
Delete compressor functioning hours
149
Command to delete compressor functioning hours
Pb1
Cabinet temperature
Pb2
Auxiliary temperature
6
SETTINGS
6.1
Setting configuration parameters
1.
Tap the SET key for 4 s. The display shows the label "PA".
2.
Tap the SET key.
3.
Tap the UP or DOWN key within 15 s to set the password. The
default password is "-19".
4.
Tap the SET key or do not operate for 15 s. The display shows the
label "SP".
5.
Tap the UP or DOWN key to select a parameter.
6.
Tap the SET key.
7.
Tap the UP or DOWN key within 15 s to set the value.
8.
Tap the SET key or do not operate for 15 s.
9.
Tap the SET key for 4 s, or do not operate for 60 s, to exit the
procedure.
6.2
Restoring the default factory settings and storing customized settings as
default
Important
- Check that the factory settings are appropriate; see CONFIGURATION PARAMETERS.
- When you store customized settings, you overwrite the default.
Tap the SET key for 4 s. The display shows the label "PA".
1.
2.
Tap the SET key.
3.
Tap the UP or DOWN key within 15 s to set the value.
VAL.
DESCRIPTION
149
Restores the default factory settings
1 = °F
161
Stores customized settings as default
Tap the SET key or do not operate for 15 s. The display shows the
1 = Hot gas
4.
label "dEF" when you set the value "149" or the label "MAP"
when you set the value "161".
5.
Tap the SET key.
6.
Tap the UP or DOWN key within 15 s to set "4".
OFF
FLASHING
Compressor off
- Compressor protection active
- Setpoint setting active
-
- Defrost delay active
- Dripping active
Evaporator fan off
Evaporator fan stop active
-
Cabinet light on by digital input
-
-
-
-
Device on
Device on or off active
7.
Tap the SET key or do not operate for 15 s. The display shows "-
- -" flashing for 4 s, then the device exits the procedure.
8.
Interrupt the power supply to the device.
9.
Tap the SET key 2 s before step 6. to exit the procedure
beforehand.
7
ALARMS
COD.
DESCRIPTION
RESET
REMEDIES
Pr1
Cabinet probe alarm
Automatic
- Check P0
Auxiliary probe alarm
Automatic
- Check probe integrity
Pr2
- Check electrical connection
AL
Low temperature alarm
Automatic
Check A1
AH
High temperature alarm
Automatic
Check A4
Open door alarm
Automatic
Check i0 and i1
id
High condenser temperature
Automatic
Check C6
COH
warning
CSd
High condenser temperature
Manual
- Switch the device off and on
alarm
- Check C7
iA
Multi-purpose input alarm
Automatic
Check i0 and i1
dFd
Defrost timeout alarm
Manual
- Tap any key
- Check d2, d3, and d11
8
ELECTRICAL RATINGS
Output
Units
cULus (UL 60730)
Applied voltage at 60 Hz
120 VAC
K1
Resistive amperes
12
compressor
Inductive amperes
relay
Full load amperes
10
Locked rotor amperes
60
K2
Resistive amperes
8
defrost or
Inductive amperes
evaporator
Full load amperes
4.4
fan or
Locked rotor amperes
26.4
configurable
relay
9
TECHNICAL SPECIFICATIONS
Purpose of the control device
Function controller
Construction of the control device
Built-in electronic device
Container
Black, self-extinguishing
Category of heat and fire resistance
D
Measurements
75 mm x 33 mm x 59 mm (2 15/16 in. x 1
5/16 in. x 2 5/16 in.)
Mounting methods for the control device
Fit the controller to a panel with the snap-in
brackets supplied
Degree of protection provided by the covering IP65 in front
Connection method
Fixed screw terminal blocks for wires up to
2.5 mm²
Maximum permitted length for connection cables
Power supply: 10 m (32.8 ft)
Analog inputs: 10 m (32.8 ft)
Digital inputs: 10 m (32.8 ft)
Digital outputs: 10 m (32.8 ft)
Operating temperature
From 0°C to 55°C (from 32°F to 131°F)
Storage temperature
From -25°C to 70°C (from -13°F to 158°F)
Operating humidity
Relative humidity without condensate from
10% to 90%
Pollution status of the control device
2
Compliance
Europe
Johnson Controls declares product compliance meets requirements of EMC,
LVD, and RoHS Directives.
USA
UL Recognized Component, SDFY2.SA516; FCC Part 15 Subpart B Class A
Canada
UL Recognized Component, SDFY8.SA516; ICES-003 Class A
Power supply
TC3B22N7x
230 VAC (+10% -15%), 50/60 Hz (+/- 3Hz), max. 2 VA
Grounding methods for the control device
None
Rated impulse-withstand voltage
4 KV
Over-voltage category
III
Software class and structure
A
Analog inputs
2 for NTC probes (cabinet probe and auxiliary
probe)
NTC probes
Sensor type
ß3435 (10 kohm at 25°C, 77°F)
Measurement field
-40°C to 105°C (-40°F to 221°F)
Resolution
0.1°C (1°F)
Digital inputs
1 dry contact (door switch/multi-purpose)
Dry contact
Contact type
Power supply
Protection
Digital outputs
2 electro-mechanical relays
Type 1 or Type 2 actions
Type 1
Additional features of Type 1 or Type 2 actions C
Display
3-digit custom display with function icons
10
PRODUCT WARRANTY
This product is covered by a limited warranty, details of which can be found at
www.johnsoncontrols.com/buildingswarranty
11
SOFTWARE TERMS
Use of the software that is in (or constitutes) this product, or access to the cloud, or hosted
services applicable to this product, if any, is subject to applicable end-user license, open-
source software information, and other terms set forth at www.johnsoncontrols.com/techterms.
Your use of this product constitutes an agreement to such terms.
12
SINGLE POINT OF CONTACT
APAC
Europe
JOHNSON CONTROLS
JOHNSON CONTROLS
C/O CONTROLS PRODUCT
WESTENDHOF 3
MANAGEMENT
45143 ESSEN
NO. 32 CHANGJIJANG RD NEW
GERMANY
DISTRICT
WUXI JIANGSU PROVINCE
214028
CHINA
13
CONTACT INFORMATION
Contact your local branch office:
www.johnsoncontrols.com/locations
Contact Johnson Controls:
www.johnsoncontrols.com/contact-us
Important
The device must be disposed of according to local regulations governing the collection
of electrical and electronic waste.
This document and the solutions contained therein are the intellectual property of Penn and thus
protected by the Italian Intellectual Property Rights Code (CPI). Penn imposes an absolute ban on the
full or partial reproduction and disclosure of the content other than with the express approval of Penn.
The customer (manufacturer, installer or end-user) assumes all responsibility for the configuration of the
device. Penn accepts no liability for any possible errors in this document and reserves the right to make
any changes, at any time without prejudice to the essential functional and safety features of the
equipment.
CE (EN 60730)
240 VAC
240 VAC
12
10
2
10
60
8
5
2
2.9
17.4
5 VDC, 1.5 mA
None
None
NA/SA
JOHNSON CONTROLS
507 E MICHIGAN ST
MILWAUKEE WI 53202
USA
loading

Inhaltszusammenfassung für Johnson Controls PENN TC3B22

  • Seite 1 Tap the SET key or do not operate for 15 s. Pollution status of the control device Compliance Europe Johnson Controls declares product compliance meets requirements of EMC, Activating manual defrost (if r5 = 0, default) LVD, and RoHS Directives. Check that the keypad is not locked.
  • Seite 2 Kontaktujte místní pobočku výrobce: Obnovení továrního nastavení a uložení zákaznicky upravených nastavení jako V následující tabulce jsou uvedené doporučené konfigurační parametry pro první www.johnsoncontrols.com/locations výchozích použití. Kontaktujte společnost Johnson Controls: PAR. VÝCH. PARAMETR MIN. - MAX. www.johnsoncontrols.com/contact-us Důležité Žádaná hodnota r1 - r2 - Zkontrolujte, zda tovární...
  • Seite 3 Aktivering af manuel afisning (hvis r5 = 0, standard) Overensstemmelse Kontrollér, at tastaturet ikke er låst. Europe Johnson Controls erklærer, at produktet opfylder kravene i EMC-, LVD- og DANSK RoHS-direktiverne. Tryk på OP-tasten i 2 sek. UL-anerkendt komponent, SDFY2.SA516; FCC del 15, underdel B, klasse A...
  • Seite 4: Technische Spezifikationen

    Zulassungen weit wie möglich von den Signalkabeln entfernt an. Wenn Sie den Parameter bearbeiten können, drücken Sie die Johnson Controls erklärt, dass die Produktkonformität den Anforderungen Europa AUFWÄRTS- oder ABWÄRTS-Taste, um zu dem gewünschten der EMV-, NSR- und RoHS-Richtlinien entspricht.
  • Seite 5: Especificaciones Técnicas

    Encendido o apagado de la iluminación del armario (si u0 = 3) Europa Johnson Controls declara que este producto cumple los requisitos de las magnético, o en ubicaciones expuestas a luz solar directa, lluvia, humedad, polvo Pulse la tecla de ENCENDIDO/ESPERA.
  • Seite 6: Caractéristiques Techniques

    Contact de porte ou multi-fonction Conformité Menu des fonctions supplémentaires Armoire Johnson Controls déclare que ce produit est conforme aux exigences des Europe Utiliser le menu des fonctions supplémentaires pour parcourir les étiquettes indiquées dans le directives CEM, LVD et RoHS.
  • Seite 7 Conformità inferiore alla soglia d2. Europa Johnson Controls dichiara che la conformità del prodotto soddisfa i requisiti PRECAUZIONI DI INSTALLAZIONE delle direttive EMC, LVD e RoHS. Assicurarsi che lo spessore del pannello sia compreso tra 0,8 mm e 2,0 mm (1/32" e Accensione o spegnimento della luce quadro (se u0 = 3) Componente omologato da UL, SDFY2.SA516;...
  • Seite 8 Naleving van wet- en regelgeving TECHNISCHE SPECIFICATIES zijn vermeld. Europa Johnson Controls verklaart dat de producten voldoen aan de vereisten van de Installeer het apparaat niet in de buurt van warmtebronnen, apparatuur met een sterk EMC-, Laagspannings- en RoHS-richtlijnen. Kastverlichting in- of uitschakelen (als u0 = 3)
  • Seite 9 Kontrollenhetens forurensingsstatus Samsvar Aktivere manuell avriming (hvis r5 = 0, standard) Europa Johnson Controls erklærer at produktene oppfyller kravene i EMC-, LVD- og Sjekk at tastaturet ikke er låst. RoHS-direktivene. Klikk på piltasten opp i 2 sekunder. UL-godkjent komponent, SDFY2.SA516, FCC del 15 kapittel B klasse A...
  • Seite 10 Zapewnić, że warunki pracy mieszczą się w granicach podanych w SPECYFIKACJE niż próg d2. Zgodność TECHNICZNE. Firma Johnson Controls oświadcza zgodność produktu z wymaganiami Europa Nie montować urządzenia w pobliżu źródeł ciepła, sprzętu o silnym polu magnetycznym, Włączanie i wyłączanie światła szafy (jeśli u0 = 3) dyrektyw EMC, LVD i RoHS.
  • Seite 11 Certifique-se de que as condições de trabalho se encontram dentro dos limites Europa A Johnson Controls declara que a conformidade do produto cumpre aos estabelecidos em ESPECIFICAÇÕES TÉCNICAS. requisitos das Diretivas CEM, LVD e RoHS. Ligar ou desligar a luz do armário (se u0 = 3) Não instale o dispositivo perto de fontes de calor, equipamento com campo magnético...
  • Seite 12 Manuaalisen sulatuksen aktivoiminen (jos r5 = 0, oletus) Vaatimustenmukaisuus Tarkista, ettei näppäimistöä ole lukittu. Eurooppa Johnson Controls ilmoittaa, että tuote täyttää EMC-, LVD- ja RoHS-direktiivien SUOMI vaatimukset. Paina YLÖS-näppäintä 2 sekunnin ajan. UL Recognized Component, SDFY2.SA516; FCC Part 15 Subpart B Class A –...
  • Seite 13 SVENSKA Tryck på UPP-knappen i 2 sek. Europa Johnson Controls försäkrar härmed att denna produkt följer kraven enligt EMC-direktivet, lågspänningsdirektivet och RoHS-direktivet. Styrenhet för normala enheter och enheter med låg temperatur Om P4 = 1 (standard) aktiveras avfrostningen om förångartemperaturen är lägre än UL-erkänd komponent, SDFY2.SA516.
  • Seite 14 Penn | TC3B22 | Installation Guide Rev. A | Part No. 24-7664-03868 | Page 14 of 14 | January 20, 2022...