5.
"Se
"Sensor
Values of all connected sensors are displayed.
Note: Number of the displayed sensors depends on the controlled
board
"Supply air temperature" °C
"Room air temperature" °C
"Extracted air temperature" °C
"Ambient air temperature" °C
"Exhaust air temperature" °C
"Return water temperature" °C
"Preheater temperature" °C
"Supply air humidity" %
"Extracted air humidity" %
"Ambient air humidity" %
"Supply air pressure" %, Pa
"Extracted air pressure" % Pa
"Extracted CO2" %, ppm
"Heating" %
"Cooling" %
"By-pass valve" %
6.
"Ad
"Additional"
Additional settings from the controlled recuperator.
6.1.
"Exit" – return to the menu window
6.2.
"ModBus" – settings of the ModBus protocol
6.2.1. ModBus network address "MBAddress" 0–247
6.2.2. Parity settings "Parity", None, Odd, Even
6.2.3. ModBus network transmission speed "Baudrate".
6.2.4. Number of the Stop bits: 1 or 2 stop bits
6.3.
"Vent.Ctrl."
6.3.1. "Mode" – select the type of ventilation:
6.3.2. "Min Supply" – lowest allowed supply temperature,
6.3.3. "Max Supply" – highest allowed supply temperature,
6.3.4. "OutDoot T.C" – summer/winter temperature setting,
6.4.
"Cool.Ctrl." – cooling control
6.4.1. "Min Supply" – minimum supply air temperature when
6.4.2. "Dx coolON" – chlorofl uorocarbon cooling is switched
20
Downloaded from
www.Manualslib.com
EN
DE
FR
preview"
Possible data transmission speeds: 2400, 4800, 9600,
19200, 38400 kbps
"Supply" – based on the supply air temperature
"Room" – based on the extracted air temperature
"ByOutDoor" – ventilation operates using the supply or
extracted air temperature based on the set "OutDoot
T.C" value of the ambient air temperature (see 6.3.4.).
When the ambient air temperature exceeds the set
value, ventilation operates using the extracted air
temperature and, when the ambient air temperature is
lower than the set temperature, supply air temperature
is used.
12–24 °C
25–40 °C
10–30 °C
cooled, 0–15 °C
on at "Cool PI", %
manuals search engine
System V2.2
Date - Time
View Alarms
Languages
View sensors
Extra
View sensors
Exit
Effi ciency
Supply air temp.
Extract air temp.
Outdoor air temp.
Extra
Exit
ModBus
Vent. Ctrl.
Coll. Ctrl.
Add. Func.
100%
Cool PI
DX_ON
DX_OFF
www.ventmatika.com
6/7
76 %
20.2 °C
19.2 °C
-2.3 °C
1/10
76 %
20.2 °C
19.2 °C
-2.3 °C
0%