3. Conformity with
standards
Luminaire for emergency ligh-
ting acc. to EN 60 598-2-22 for
connection to safety luminaire
systems acc. to DIN VDE 0100-
718, EN 50 172 and E DIN VDE
0108-100. Used ECG is conform
to:
EN 60 929, EN 61 347-2-3 and
EN 61 347-2-4.
Designed, manufactured and
tested according to DIN EN ISO
9001.

4. Technical data

Power input:
220-240 V AC
50/60 Hz
176 - 275 V DC
Standby power loss: < 0.5W
Power factor:
0.6
Inrush current: 3A/ms
Operating frequency: 44 kHz
Rated current (AC): 60 mA
Power con-
sumption (AC): max. 15 VA
Rated current (DC): 30 mA
Lamp:
8 W acc. to
81-IEC-1040-1
Rated luminous flux of
the lamp:
450 lm
Rated luminous flux for emer-
gency operation: 75 % (phi
Insulation class:
II
Protection category acc.
to EN 60529:
IP 41
option:
IP 54
Perm. ambient
temperature:
- 10 °C ..+ 40°C
Supply
terminals:
3 x 2 x 2.5 mm²
Weight:
0.85 kg
(single side)
1.0 kg (two-sid.)
Dimensions:
see dimensio-
nal drawing in
page 6
4.1 Brief description/
Scope of application
Exit or safety luminaire, suitable
for operation on CEAG safety
lighting systems with single
luminaire monitoring (Cewa-
Guard-Technology) and/or with
programmable switching mode
in the outgoing circuit (STAR-
technology).
The Style 55011,-021 is not
fitted with monitoring electronic
and so neither addressable nor
switchable.

5. Installation

For the mounting and
operation of electrical
apparatus, the res-
pective national safety regula-
tions as well as the general
rules of engineering will have to
be observed.

5.1 Mounting

After fixing the quick mounting
plate in accordance with the re-
spective instructions, the mains
connection (L (U), N (0), PE) is to
be established (fig. 5). Pay atten-
tion to a tight fit of the terminal
screws! Unused cable entries are
left with their locking plug fitted
(IP protection).
In order to fix the luminaire, the
opening in the body of the lu-
minaire is placed on the guide
pin (fig. 1) of the quick assem-bly
plate. Then all four corners of the
body of the luminaire are pushed
down until they distinctly lock in
on the quick mounting plate (the
snap hooks engage in the quick
)
mains
mounting plate). When installing
the luminaire with IP 54 protec-
tion, the IP 54 accessories kit is
to be fixed with 4 screws.
For lamp replacement or ad-
dressing, the snap hooks of the
screen are detached with a slot-
ted screw driver (fig. 6).
In order to detach the body of
luminaire from the quick moun-
ting plate, a slotted screw driver
is inserted into the lateral recess
on the reflector (fig. 7). Through a
slight lateral lever action towards
the outer edge, the snap hook is
released. When slightly pulling
the body of luminaire from the in-
side, it disengages from the quick
mounting plate. After having re-
leased all four snap connections,
the body of luminaire can
be removed from the quick
mounting plate; in case of the IP
54 version the 4 screws will have
to be unscrewed.

5.2 Mounting accessories

Pendulum set
(CEAG No. 400 71 345 972)
Wall bracket
(CEAG No. 400 71 345 974)
Quick mounting plate
(CEAG No. 400 71 345 974)
Chain suspension
(CEAG No. 400 71 345 973)
Wire guard
(CEAG Nr. 400 71 348 370)
IP 54 accessories kit
(CEAG Nr. 400 71 345 975)
The attached mounting
instructions CEAG
No. 300 80 001 428
have to be observed.
5.3. Addressing
(only STYLE 57.. CG)
Before fitting the screen or
bowl, the addressing of the
individual luminaires will have
to be performed. To do so,
the desired address (1 - 20) is
set on the address switch by
means of a suitable screw dri-
ver (Arrowhead to No., fig. 8).
If the luminaire should not be
monitored the code 0/0 has to
be selected.
The luminaires STYLE 57011
and 57021 are not equipped
with monitoring circuit and will
not be addressable.
9

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Style 57021Style 57011 cg-sStyle 57021 cg-s

Inhaltsverzeichnis