2. Safety Instructions

The device shall only be used
for its intended pur-pose and
in undamaged and perfect
condition!
Only genuine CEAG spare
parts may be used for re-
placement and repair!
When working on the emer-
gency luminaire make sure
that it is disconnected from the
voltage! Pay attention to the
different power supplies in
mains or battery operation. Fig.
11 shows the indication label
on the emergency luminaire.
Prior to its initial operation, the
luminaire will have to be
checked in accordance with
the instructions as per section

Installation!

Carry out the marking of the
emergency luminaire: As-sign
the circuit, the luminaire No.
and ID-No. and enter them.
The manual log book shall be
performed in compliance with
the national regulations. It is
not applicable by automatical
log book with the CG-Con-
troller CGLine!
Any foreign matter shall be
removed from the luminaire
prior to its initial operation!
Observe the national safety
rules and regulations for pre-
vention of accidents as well as
the safety instructions included
in these operating instruction
marked with
3. Conformity with
Standards
Conforms to: EN 60 598-1,
EN 60 598-2-22, EN 1838, DIN
VDE 0108/10.89.
Low-voltage directive
93/68/EEC,
EMC directive 89/336/EEC.
Note: In spite of CE conformity,
there may be a mutual influence
on equipment and luminaires.
Developed, manufactured and
tested in accordance with DIN
EN ISO 9001.

4. Technical data

Input voltage:
230/240 V AC
50 Hz
Rated current
(AC):
70 mA
Power con-
sumption (AC): max. 16 VA
Lamp:
8 W/T16
Rated lumi-
nous flux of
the lamp:
450 lm
Rated lumi-
nous flux:
40% (phi
at the end of operating cycle
Insulation
class:
I
Protection
category acc.
to EN 60529:
IP 65
Accu:
gas-tight,reloadable,
maintenance-free
Rated operating cycle:
1h: NC-accu 3,6V, 1,5Ah
3h: NC-accu 3,6V, 4,0Ah
Admissible ambient
temperature
maintained light
- 5°C...+35°C
non maintained light 0°C...+30°C
Supply
terminals:
3 x 2,5 mm²
Bus terminals
2 x 1,5 mm
Weight 68011-1/D IP41
68011-3/D IP41
Dimensions: see dimensional
drawing on page 3
9
Fig. 11
4.1 Brief Description/Area of
Application
As a self-contained luminaire
the CGLine 6811 emergency
and safety luminaire is suitable
for installations according to
VDE 0108.
With the CEAG CG-Controller
CGLine 400 the self-contained
luminaires can be monitored
centrally via a bus cable.
5.Installation
regulations as well as the
general rules of engineering will
have to be observed.
/phi
)

5.1 Assembly

E
nominate
To open the luminaire use a
screwdriver and remove the
screws on each side of the
luminaire (Fig. 3).
By loosening the two screws
(Fig. 4) the electrical fitting
snappes out.
By means of two bore holes in
the back plane (Fig. 5) of the
luminaire (300 mm distance)
the luminaire can be fixed.
cable entry please use the M20
screwing (Fig. 6). In case of
through connection the locking
screw (Fig. 7) has to be
exchanged for a M20 screwing.
2
If an entry is not used, leave
2,2kg
the sealing stopper (IP degree
2,4kg
of
protection).
To ensure the IP-protection
appropriate screws must be
used (5 mm). For IP-protection
use the enclosed sealing discs.
For the mounting and
operation of electrical
apparatus, the res-
pective national safety
For

Werbung