Salda FLEX Serviceanleitung Seite 3

Steuerungspult mit lcd-bildschirm
Vorschau ausblenden Andere Handbücher für FLEX:

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

EN
8.2.
"Night T" - {0-15}°C minimum outdoor air temperature
8.3.
"Room T" - {10-30}°C indoor air temperature
9.
"Wheat" - temperature settings of the water heater
9.1.
"W_crit" – {„Watter stop"+5, 20}°C The limit from which the temperature of the return water is
forced to be increased
9.2.
"W_stop" - {-10 „Watter crit"-5}°C The limit at which fans are stopped
9.3.
"Pump stop" - {10-30}min. Time after which the water pump is switched off if there is no need for
heating
9.4.
"Exercise" - {0-5}h. The period for preventive start of the water pump „Pump_stop" time
10. "Act" – select the basic settings of the unit.
NOTICE! Leaving this paragraph the unit and the controller reloads.
10.1. "Heater" – {E_On/Off, E_0_10, E_ESKM, W_VAL+-, W_0_10}
E_On/Off – the electric heater is On/Off controlled using the relay
E_0_10 – the electric heater is controlled using 0–10 V output
E_ESKM – TRIAC control of the electric heater
W_VAL+ - Control of the three-position actuator of the water heater
W_0_10 – Control of the 0–10 V actuator of the water heater
10.2. "Exch" – {R_0_10, R_On/Off, B_0_10, B_DMP}
R_0_10 – 0–10V control of the rotor heat exchanger
R_On/Off – On/Off control of the rotor heat exchanger using the relay
B_0_10 – 0–10 V control of the bypass valve of the plate hater exchanger
B_DMP – Control of the three-position bypass valve of the plate heat exchanger
10.3. "VentUnit" – {TK, RHEC, RHC}
TK – Supply chamber, section 10.2 is not applicable
RHEC – Recuperator with the heat exchanger control
RHC – Recuperator without the heat exchanger control
10.4. "Fans Tipe" – - {EC_0_100, EC, AC}
EC_0_100 -
EC – control of the EC motors using 0–10 V signal
AC – control of the AC motors using three fixed voltages
11. "PSI." – when pressure support is selected, min. and max. limits are set for the pressure converter
11.1. "min_0V" – {0ppm–2000} % Pa
11.2. "max_10V" – {0ppm–2000} %, Pa
12. "CO2" – when CO2 control is selected, min. and max. limits are set for the CO2 converter
12.1. "min_0V" – {0ppm–2000} %, ppm
12.2. "max_10V" – {0ppm–2000} %, ppm
12.3. "PPM_100%" - {20-255}*100ppm
13. "VentCtrl" – setting of the indications for fans
13.1. "SAF" – {Percent, Pressure} settings for the indications of the supply air motor %, Pa, factory set-
ting (Percent)
13.2. "EAF" – {Percent, Pressure, SAF+Pressure} settings for the indications of the extracted air motor
%, Pa
13.3. "SAF+Pressure" – extracted air motor change differs from the supply only by the set value
13.4. "CO2" – {On/Off} extracted air CO2 sensor
13.5. "ResetToFactorySettings" – after switching "OK", factory settings are saved.
NOTICE! The unit and the controller reloads.
14. "Misc" – stop conditions for the unit depending on the connection of the controller
14.1. "RC NC" – {On, Off}, factory setting (Off)
On – (Remote Control) No control panel, the unit is stopped
12
www.salda.lt