Herunterladen Diese Seite drucken

Honeywell NOTIFIER LT-200 NFXI-ASD Serie Kurzanleitung Seite 12

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 45
APPENDIX B - PRACTICAL PIPE DESIGNS for ASPIRATING SYSTEMS
The following tables show some typical EN54
compliant pipe designs for FAAST LT-200
devices with different overall pipe lengths.
Each design has a one size sample hole for
ease of installing and testing the system.
No exhaust pipe has been included in these
designs.
In all the suggested layouts, the sample hole
spacing is set to 10m between holes, which
is the recommended arrangement for point
smoke detectors in the UK (BS 5839). Air
flow through the detector has been kept at, or
above, 39 l/min for best performance.
In the designs with non-sensing end holes,
the distance to the first hole is 9m and the
end hole is 1m from the last sample hole.
N200-102-01
CLASS C PIPE DESIGNS WITH SINGLE SAMPLE HOLE/END HOLE SIZE AND 10m SPACING 
Pipe 
Number 
Hole 
Length 
of holes 
size 
(m)
(mm)  (mm)  (I/min)
100 
10 
90 
80 
3.5 
70 
3.5 
60 
50 
4.5 
40 
4.5 
30 
20 
5.5 
10 
6.5 
* Non‐sensing end hole
CLASS C PIPE DESIGNS WITH SINGLE SAMPLE HOLE/END HOLE SIZE AND 10m SPACING 
Per pipe 
Number 
Hole 
length 
of holes 
size 
(m)
(mm)  (mm)  (I/min)
80 
2.5 
70 
2.5 
60 
50 
40 
3.5 
30 
3.5 
20 
10 
* Non‐sensing end hole
CLASS C PIPE DESIGNS WITH SINGLE SAMPLE HOLE SIZE (Inc. SAMPLING END HOLE) 
Pipe 
Number 
Hole 
Length 
of holes 
size 
(m) 
(mm)  (I/min) 
100 
‐ 
90 
‐ 
80 
3.5 
70 
60 
4.5 
50 
5.5 
40 
30 
6.5 
20 
6.5 
10 
‐ 
X: No adequate or recommended single sample hole size design 
12
1 PIPE 
End 
Air 
Flow 
hole* 
flow 
balance
40 
0.5 
39 
0.53 
3.5 
43 
0.52 
3.5 
42 
0.62 
45 
0.6 
4.5 
45 
0.62 
4.5 
45 
0.76 
46 
0.83 
5.5 
45 
0.92 
6.5 
45 
2 PIPE (T FORM) 
End 
Air 
Flow 
hole* 
flow 
balance
2.5 
47 
0.71 
2.5 
45 
0.77 
46 
0.72 
45 
0.81 
3.5 
45 
0.81 
3.5 
44 
0.91 
44 
0.95 
45 
AND 10m SPACING ‐ 1 PIPE 
Air 
Flow 
Average 
flow 
balance 
sensitivity 
(%/m) 
‐ 
‐ 
‐ 
‐ 
42 
0.6 
0.79 
44 
0.58 
0.70 
44 
0.59 
1.00 
45 
0.54 
0.86 
44 
0.65 
0.67 
45 
0.78 
0.99 
44 
0.92 
1.31 
‐ 
‐ 
Average 
Alarm 
Fan  Total hole 
sensitivity
level 
(%/m) 
0.74 
10 
0.66 
10 
0.91 
10 
0.79 
10 
1.14 
10 
0.98 
0.80 
10 
1.29 
10 
0.97 
10 
1.31 
10 
Average 
Alarm 
Fan  Total hole 
sensitivity
level 
(%/m) 
1.16 
1.03 
0.91 
1.16 
0.97 
1.30 
0.98 
1.31 
Alarm 
Fan 
level 
hole area 
‐ 
‐ 
‐ 
‐ 
‐ 
‐ 
10 
10 
10 
‐ 
‐ 
‐ 
I56-6577-008
area 
(mm
2
77.76 
70.70 
86.60 
76.98 
87.98 
95.44 
79.53 
78.55 
71.28 
66.37 
area 
2
(mm
83.46 
73.64 
91.90 
77.76 
86.60 
67.36 
62.84 
58.91 
Total 
(mm
2
‐ 
‐ 
76.98 
87.98 
95.44 
118.81 
113.11 
99.56 
66.37 
‐ 

Werbung

loading