INSTALLATION AND MAINTENANCE INSTRUCTIONS
MI-LPB2-S2I REFLECTED TYPE PROJECTED BEAM
SMOKE DETECTOR
GENERAL
The model MI-LPB2-S2I is an addressable long range projected beam
smoke detector designed to provide open area protection. It consists of
a combined transmitter/receiver unit and a reflector. Smoke entering the
area between the two components causes a reduction in the signal
returned to the receiver.
When the obscuration reaches the alarm
threshold, selected at the transmitter/receiver unit, the detector
generates an alarm signal. Complete blockage of the beam causes a
fault signal. Slow changes in obscuration due to a build up of dirt or dust
on the lens of the detector are compensated for by a micro-controller
that continuously monitors the signal strength and periodically updates
the alarm and fault thresholds.
reaches its limit, the detector generates a fault signal, indicating the need
for service. After local testing is complete, the yellow LED will blink a
pattern to indicate the level of drift compensation employed during the
test (see Blinks Output by Yellow LED table at back of manual).
SPECIFICATIONS
General
Range:
Sensitivity:
Maximum angular misalignment
Environmental
Temperature:
Humidity:
Mechanical
Dimensions (Without Faceplate):
Dimensions (With Faceplate):
Wiring:
Adjustment Angle:
Electrical
Voltage:
Avg. Standby Current:
Advanced Protocol Mode:
Max. Alarm Current (LED on):
Max. Fault Current (LED on):
Max. Alignment Current:
External Supply
Remote Output (alarm):
PARTS LIST
Description
Transmitter/Receiver Unit
Paintable Trim Ring
Reflector (REFL6500)
Plug-in Terminal Blocks
Isolator Shunts
Orange Alignment Assistance Label
Instruction Manual
MB200-00-02
When the self-compensation circuit
5 to 70m
70 to 100m using optional
accessory 6500-LRK/BEAMLRK
Level 1 = 25% (1.25dB)
Level 2 = 30% (1.55dB)
Level 3 = 40% (2.22dB)
Level 4 = 50% (3.01dB)
Level 5 = 30% to 50% Adjusting
(Acclimate)
Level 6 = 40% to 50% Adjusting
(Acclimate)
Detector ± 0.5°
Reflector ± 10°
-30°C to 55°C
10% to 95% Relative Humidity
(Non-condensing)
229mm x 178mm x 84mm
253mm x 193mm x 84mm
0.3 mm² to 3.2 mm²
±10° Horizontal and Vertical
15 to 32 VDC (15-28.5V when
using isolators)
2mA @ 24VDC; 1 comm. every
5sec, LED flashing.
Read 16 sec. LED blink 8 sec
8.5mA
4.5mA
20mA
Voltage:
15 to 32 VDC
Current:
0.5A Max.
Voltage:
15 to 32VDC
Current:
6mA to 15mA.
Limited by 2.2KΩ resistor
Quantity
1
1
1
3
2
1
1
APPROVED ACCESSORIES
6500-LRK/BEAMLRK
Long Range Kit comprising three additional 20cm x 20cm reflectors,
which may be mounted in a square with the supplied reflector, permitting
the detector to be used for ranges from 70m to 100m.
6500-MMK/BEAMMMK
Multi-Mounting Kit allowing the MI-LPB2-S2I to be mounted to ceilings, or
to walls where the detector and reflector cannot be mounted within 10° of
one another.
One kit mounts either the transmitter/receiver unit or
reflector. If the transmitter/receiver is mounted on the MMK, then the
6500-SMK/BEAMSMK must be used. Note that only a single 20cm x
20cm reflector can be mounted using the MMK:
BEAMLRK is not compatible with the MMK.
6500-SMK/BEAMSMK
Surface Mounting Kit for the transmitter receiver (also used in
combination with the 6500-MMK/BEAMMMK) to give an additional 43mm
depth to assist surface mounting and to permit side entry cabling.
RTS151KEY
Remote annunciator accessory providing a reset function, it has a Red
LED to indicate alarm conditions (Note: Back-box, if required, needs to be
ordered separately - part number WM2348).
DETECTOR MOUNTING
Location
The MI-LPB2-S2I must be located in accordance with local standards
and guidelines, for example BS5839 part 1. For general information,
refer to the application guide for projected beam smoke detectors
available on request from your supplier.
Mounting Position
Beam detectors require a very stable mounting surface for proper
operation. A surface that moves, shifts, vibrates, or warps over time
may cause false alarm or fault conditions. Initial selection of a proper
mounting surface will eliminate nuisance alarms and fault signals. Mount
the detector on a stable mounting surface such as brick, concrete, a
sturdy load-bearing wall, support column, structural beam, or other
surface that is not expected to experience vibration or movement over
time. DO NOT MOUNT the beam detector on corrugated metal walls,
sheet metal walls, external building sheathing, external siding,
suspended ceilings, steel web trusses, rafters, non-structural beam,
joists, or other such surfaces.
tolerance to movement than the transmitter/receiver, hence in cases
where only one stable mounting surface as defined above can be used,
the transmitter/receiver unit should be mounted to the stable surface.
See specifications for maximum permissible angular misalignment;
movement outside these limits may cause nuisance alarms and faults.
Mounting Considerations
There must be a permanent clear line of vision between the detector
and the reflector.
Reflective objects should be a minimum of 380mm from the line of
sight between the detector and reflector to avoid compromise of the
protected area by reflected light.
Direct sunlight or strong lights into the transmitter/receiver unit
should be avoided. There should be a minimum of 10° between the
paths of the light source and the detector beam.
Operation of the detector through panes of glass should be avoided
if possible. If it is necessary to pass though glass, the angle between
the beam and glass should be set a minimum of 10° off perpendicular,
and operation through multiple panes should be avoided.
MOUNTING
The transmitter/receiver unit may be mounted directly to the wall, with
rear cable entry. The detector base has four primary mounting holes,
one in each corner of the base. All four holes must be used to provide
secure mounting. In order to mount the detector to the wall, the outer
cover must be removed after unscrewing it's four retaining screws.
1
The 6500-LRK/
The reflector has a much greater
I56-3879-000

Werbung

Inhaltsverzeichnis
loading

Inhaltszusammenfassung für Honeywell MORLEY IAS FIRE SYSTEM MI-LPB2-S2I

  • Seite 19: Installations- Und Wartungsanleitung Linearer Rauchmelder Mi-Lpb2-S2I Mit Prismen-Reflektor

    INSTALLATIONS- UND WARTUNGSANLEITUNG LINEARER RAUCHMELDER MI-LPB2-S2I MIT PRISMEN-REFLEKTOR ALLGEMEIN Der Lineare Rauchmelder MI-LPB2-S2I ist ein ringbusgespeister VOM HERSTELLER ZUGELASSENES ZUBEHÖR Langstrecken-Melder und wird zur Überwachung von offenen Bereichen eingesetzt. Der Melder besteht aus einer Sender-/Empfänger-Einheit sowie 6500-LRK/BEAMLRK einem Prismen-Reflektor. Die Auslösung des Melders erfolgt bei Langstrecken-Zubehör, bestehen drei...
  • Seite 20 Die Verkabelung des Melders wird durch das Installationszubehör 6500- SMK/BEAMSMK oder 6500-MMK/BEAMMMK erleichtert. Weiter-führende Informationen sind der jeweiligen Installationsanleitung zu entnehmen. SCHRAUBEN ZUR WANDBEFESTIGUNG GEHÄUSESCHRAUBEN Abbildung 1: Wandmontage der Sender-/Empfänger-Einheit Der Prismen-Reflektor- wird mittels der vier Befestigungslöcher in jeder 1 2 3 4 1 2 3 4 1 2 3 4 Ecke, direkt auf der Montagefläche befestigt.
  • Seite 21: Adressierung

    • Stellen Sie sicher, dass sich keine Objekte zwischen dem Melder und dem Prismen-Reflektor befinden. Weiterhin dürfen sich im näheren Umfeld seitlich zur Strahlachse (mindestens 380mm) keine reflektierenden Objekte befinden. • Stellen Sie sicher, dass die Achswinkel des Melders und des Prismen-Reflektors eingehalten werden.
  • Seite 22: Einstellung Der Empfindlichkeit

    Schritt 3. End-Verstärkungseinstellung Siehe Abbildung 9. In diesem Schritt erfolgt die endgültige Einstellung der Verstärkung. Für diesen Schritt ist es erforderlich, das Gehäuseoberteil wieder zu montieren, AUGE da sich die Empfangseigenschaften des reflektierten Lichts hierdurch verändern. Montieren Sie das Gehäuseoberteil des Melders. Das Gehäuseoberteil wird mittels der vier Gehäuseschrauben in den Ecken befestigt.
  • Seite 23: Empfindlichkeitstest

    Diese beinhaltet folgende Schritte: KENNLINIE 1: MELDEREMPFINDLICHKEIT (%/m) vs 1. Überprüfen Sie alle elektrischen Anschlussleitungen, sowie die UBERWACHTUNGSSTRECKE Spannungsversorgung des Melders. 2. Stellen Sie sicher, dass der Strahlenweg nicht durch ein Hindernis versperrt ist oder durch Fremdlichtquellen inkl. reflektierende bzw. Ebene 2 glänzende Oberflächen gestört wird.
  • Seite 24 Blinkmodus der gelben LED nach einem lokalen Meldertest: Anzahl des Prozentwert Melderblinkens Driftkompensation <10% Kein <20% <30% <40% <50% <60% <70% <80% <90% <100% 0832-CPD-0329 12 EN54-12: 2002 EN54-17: 2005 MB200-00-02 I56-3879-000 Morley IAS, Charles Avenue, Burgess Hill, West Sussex, RH15 9UF, England...