Overload Relay with Phase>Failure Sensitivity
Instructions
Limited protection against contact with live parts
!
Degree of protection IP 20 to IEC 60529
Safe from finger touch to DIN VDE 0106, Part 100
Commissioning and maintenance by qualified personnel only.
Follow the operating instructions!
WARNING:
HAZARDOUS VOLTAGE
CAN CAUSE ELECTRICAL SHOCK
DISCONNECT POWER BEFORE PROCEEDING
WITH ANY WORK ON THIS EQUIPMENT.
For overload relay for individual mounting, see Fig. ¡
Installation
For dimension drawings (dimensions in mm) see Fig. ¬
For permissible installed positions, see Fig. √
Snap>on mounting on a top>head rail (35 mm) to EN 50 022 or bolting on a
plane surface by two bolts to be secured by washers and spring washers.
Do not subject to sudden shocks or long>term vibrations.
Connection
Permissible cable cross>sections
Solid/stranded
[mm
Solid
[mm
Finely stranded with end sleeve [mm
AWG conductors
Terminal screw
Tightening torque
[lb
Use copper wire 75∞ only.
For equipment circuit diagram, see Fig. ƒ
In the case of several single>phase loads, the three main circuits must be
connected in series.
Commissioning
For instructions, see Fig. ≈
— Set the scale to the rated current of load.
" Reset button (blue)
Push this button before commissioning and after tripping to make relay
ready for operation.
In the as>delivered condition, the auxiliary contact is set to H=Manual
resetting. To change from H=Manual to A=Automatic, press and turn
the button counter>clockwise from H to A.
" Test button (red)
When this button is actuated, the NC contact opens and the NO contact
closes, i.e. a test function for NC and NO contacts (simulation of over>
load tripping).
In the ∫Manual∫ position, the relay is reset when the blue button is
pressed.
In the ∫Automatic∫ position, the relay is reset automatically when the
red button is released.
' TRIPPED indication (green)
In the H setting, a green pin protrudes from the front plate to indicate
the TRIPPED condition. In the A setting, this condition is not indicated.
2
AND BURNS.
Phase
Auxiliary
conductor
conductor
2
] 1.5 to 25
2
]
2¥0.5 to 1
2¥1 to 2.5
2
] 1 to 16
2¥0.5 to 1
2¥0.75 to 2.5
16 to 3
2¥18 to 12
M5
M3.5
[Nm]
2.5 to 3.0
0.8 to 1.4
in]
22 to 26.5
7 to 12
·
DIN VDE 0660 Part 102, IEC 60947>4
Order No.: 3ZX1012>0UA51>1AA1
For tripping characteristics, see Fig. ∆
The characteristics conform to VDE 0165, VDE 0170/0171 for machines
with type of protection E Ex e.
Tripping times are shown for a three>phase load from the cold state
(ambient temperature +20 ∞C). In the case of hot relays, preloaded with
1¥I
, the tripping times decrease by approx. 25 %.
E
l
= Current setting
E
t
= Tripping time in seconds (±20 %)
A
— = Setting range
(¡=lowest value of current setting I
¬=highest value of current setting I
" = Type designation/Order No.
" = PTB (Federal testing Laboratories) Test Report No.
Technical data
Main circuit
Rated insulation voltage
Rated operational current
Permissible ambient air temperature
Suitable for use on a circuit capable of delivering not more than 5000 rms
symmetrical amperes, 600 V maximum.
For short>circuit protection
NH>, NEOZED or DIAZED fuses
According to excerpt from IEC 60947>4
DIN VDE 0660, Part 102
Type of coordination ∫1∫:
The contactor and overload relay may be damaged. If necessary, the
contactor and/or overload relay must be replaced.
Type of coordination ∫2∫:
The overload relay must not be damaged. However, contacts may be
welded as long as they can be easily separated.
Auxiliary circuit
Rated operational currents
AC>15/U
V
24
60
E
AC>15/I
A
2
1.5
E
DC>13/U
V
24
60
E
DC>13/I
A
2
0.5
E
Short>circuit protection:
NH>, NEOZED or DIAZED fuses
DIAZED fuses
Miniature circuit>breaker
Insulation rating
400 V
differing
potential
For further data and accessories, see Catalog NSK.
3UA59
,
E
)
E
690 V AC
0.1 to 63 A
> 25 ∞C to+55 ∞C
see nameplate
125
230
400
690
1.25
1.15
1.1
0.8
110
220
0.3
0.2
6 A
10 A, fast
3 A (C>characteristic)
690 V
same
potential