Description:
MODBUS/RTU module to collect 2 digital inputs for 10...250Vac/dc signals via serial bus, Host communication: via RS232 or RS485 with MODBUS/RTU slave protocol, Host baud rates: 9600, 19200, 38400 or
57600Bd, no, even or odd parity, 8 data bits, 1 stop bit, Digital inputs and serial RS232/RS85 interface are galvanic isolated, Digital inputs: Voltage: 10..250Vac/dc, Input current per channel: ~1.9mA, Configuration and
testing of module with free PC software MODBUS configurator, Weight: 55g, Dimension (LxWxH): 17,5x90x58mm, Power supply: 12-48V=, Power consumption: <0.5W, Mountable onto a EN50022 DIN rail.
Manual+Software:
To configure our module, you need our free software tool ModbusConfigurator. Read the actual manual for our product very carefully! You will find both things on our homepage
12-48V=
GND
RS232, GND
RS232, RX
RS232, TX
10-250Vdc
GND
CLAMP/LEDS
12-48V=
GND
RS232, GND
RS232, RX
RS232, TX
L
10-250Vac
N
RESI-2RI-MODBUS
L+
Power supply
M-
L+: 12-48V=
M-: Ground
A
RS485 Modbus/RTU slave
B
interface
A: DATA+
B: DATA-
RX
RS232 Modbus/RTU slave
TX
interface
M-
RX: serial receive
TX: serial transmit
M-: Ground for RS232
I1
Two digital inputs:
C
I1: digital input 1
I2
I2: digital input 2
C: common contact for both
inputs
STATE
State-LED, flashes, when
converter is ok
INFO
If one of the two digital inputs
is high, this LED in on.
HOST
HOST-LED, flashes, when
host sends/receive ASCII or
MODBUS/RTU telegrams
www.RESI.cc
Dip Switch
Description
Baudrate
Use DIP Switch 1 and 2 to select the baud rate:
BR
OFF
OFF:
9600Bd
ON
OFF:
19200Bd
OFF
ON:
38400Bd
ON
ON:
57600Bd
HINT: The correct parity (NONE; EVEN;ODD) is selected
with the software tool, not with DIP switches.
Interface
Selects the physical type of the serial interface:
IF
OFF=RS232
ON=RS485
Function
Selects a special function:
Definition
OFF=The unit ID from the FLASH memory is used
FD
ON=The unit ID is always 255
HINT
After you change a DIP switch, the converter reboots
automatically. Therefore you don't need to switch off and on
the converter to change settings. After a reboot, all three
LEDs are on for a short period to signal the power on
procedure.
Technical Conditions
0...60°C
Operating temperature
Storage temperature
-20..+80°C
Humidity
25..90 %rH not condensing
Power supply
12-48Vdc +/-10%
Power consumption
<0.5W
Clamps
Tightening torque max. 0.5Nm
Clamp Wire cross section
max. 1.5mm²
Dimension (LxWxH)
17.5x90x58mm
Weight
55g
Protection class
IP20
Conformity
CE