TECHNICAL MANUAL. START-UP AND OPERATION
B. Failures
C. R407C Gas
D. Maintenance instructions
· Do not use the load cylinder
· Use a balance and a bottle of R407C with an immersion tube
· Load the weight of R407C following the value indicated in the plate where the characteristics of the unit are specified.
· Minimize the entrance of ambient air in the circuit
· Replace the dehydrator.
· Carry out the "creation of a vacuum" to a minimum level of 0.3 mbar (static).
3. PRECAUTIONS FOR USE AND CONDITIONS OF USE
A. Safety instructions
Any incorrect manipulation may cause an important risk that could involve deadly injuries.
Any incorrect manipulation may cause serious damages to the user and the unit.
ATTENTION
WARNING