INSTALLATIoN
Commissioning
12.2 Sensor installation
12.2.1 Outside temperature sensor AF PT
The outside temperature sensors have a significant influence on
the function of your heating system. Therefore ensure that the
outside temperature sensors are correctly positioned and well
insulated.
- Install the outside temperature sensor on a north or
north-eastern wall.
- Ensure that the outside temperature sensor is freely exposed
to the elements but not placed in direct sunlight.
- Never mount the outside temperature sensor above win-
dows, doors or air ducts.
- Observe the following minimum clearances: 2.5 m above the
ground and 1 m to the side of windows and doors
Installation
f Remove the cover.
f Secure the base with the screw supplied.
f Connect the cable.
f Connect the outside temperature sensor to AA01-X1.3.
f Replace the cover. The cover must audibly click into place.
12.3 Remote control
f Please observe the commissioning instructions for the heat
pump manager.
The FET remote control is required to record humidity in the case
of cooling via an area heating system.
13. Commissioning
Our customer support can assist with commissioning, which is a
chargeable service.
If the appliance is intended for commercial use, observe the rules
of the relevant Health & Safety at Work Act during commissioning.
For further details, check with your local authorising body (in
Germany, for example, this is the TÜV).
13.1 Checks before commissioning the heat pump
manager
Material losses
!
Observe the maximum system temperature in underfloor
heating systems.
f Check that the heating system is filled to the correct pressure
and the quick-action air vent valve is closed.
f Check whether the outside temperature sensor is correctly
placed and connected.
f Check whether the power supply is connected correctly.
f Check whether the signal cable to the heat pump (bus cable)
is correctly connected.
38
| HSBB 180 Plus|HSBB 180 S Plus
High limit safety cut-out
Note
At temperatures below –15 °C the high limit safety cut-out
may respond. The appliance may be subjected to these
temperatures during storage or transport.
HSBB 180 S Plus
1 High limit safety cut-out reset button
f Check whether the high limit safety cut-out has tripped.
f If the high limit safety cut-out has triggered, reset it with the
reset button.
13.2 Commissioning the heat pump manager
Commission the heat pump manager and make all settings in ac-
cordance with the heat pump manager operating and installation
instructions.
Note
For DHW mode, ensure that the PARALLEL OPERATION
option is set in the heat pump manager. With this setting,
the cylinder charging pump / heating circuit pump is also
activated in DHW mode.
To set the heat pump manager:
f With the MENU key, call up the main menu.
f Select the menu or value and confirm with OK:
SETTINGS
DHW

STANDARD SETTING

DHW MODE
Note
On appliances with a single phase connection, set the
heat pump manager as follows for calculating the amount
of heat.
To set the heat pump manager:
f With the MENU key, call up the main menu.
f Select the menu or value and confirm with OK:
SETTINGS
HEATING

ELECTRIC BOOSTER HEATER

NUMBER OF STAGES
1
HSBB 180 (S) Plus
Value
PARALLEL OPERATION
Value
2
www.stiebel-eltron.com

Werbung