Connection type
Version
Main contacts and
auxiliary contacts
(directly on the switch)
Connection
cross-section
solid / finely
stranded
Tightening torque
Connection type
Version
147924 / 8146647300
2016-10-04·BA00·III·en·11
Connection terminals
8146/5-V..-.00-....
8146/5-V..-.01-....
2
1.5 ... 4 mm
solid
2
1.5 ... 2.5 mm
finely stranded
2
10 mm
solid
Only one conductor, which must be bend in form of a hook (see drawing), can be
installed to the connection terminal.
Caution: only possible without IP20 covering!
1.8 Nm (16 lb-in)
Connection terminals
8146/5-V..-.05-.... / 8150/5-V..-.05-....
8146/5-V..-.06-.... / 8150/5-V..-.06-....
8146/5-V..-.07-.... / 8150/5-V..-.07-....
Mounting and installation
8146/5-V..-.02-.... / 8150/5-V..-.02-....
8146/5-V..-.03-.... / 8150/5-V..-.03-....
8146/5-V..-.04-.... / 8150/5-V..-.04-....
1.5 ... 6.0 mm
One or two conductors can be installed
to one connection terminal.
Both conductors must have the same
cross-section and must be made of the
same material.
2 Nm
8146/5-V..-.08-.... / 8150/5-V..-.08-....
8146/5-V..-.09-.... / 8150/5-V..-.09-....
8146/5-V..-.10-.... / 8150/5-V..-.10-....
Safety switch / load disconnect switch
Series 8146/5-V37, Series 8150/5-V37,
Series 8146/5-V11
2
15518E00
35