Herunterladen Diese Seite drucken

Qlima WDH JA 4122 Gebrauchsanweisung Seite 92

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
1.7 Ventilated area
Ensure that the area is in the open or that it is adequately ventilated before
breaking into the system or conducting any hot work. A degree of ventilation
shall continue during the period that the work is carried out. The ventilation
should safely disperse any released refrigerant and preferably expel it extemally
into the atmosphere.
1.8 Checks to the refrigeration equipment
Where electrical components are being changed, they shall be fit for the purpose
and to the correct specification. At all times the manufacturer's maintenance
and service guidelines shall be followed. lf in doubt consult the manufacturer's
technical department for assistance. The following checks shall be applied to
installations using flammable refrigerants: - the charge size is in accordance with
the room size within which the refrigerant containing parts are installed;
• the ventilation machinery and outlets are operating adequately and are not
• if an indirect refrigerating circuit is being used, the secondary circuit shall be
• marking to the equipment continues to be visible and legible. Markings and
• refrigeration pipe or components are installed in a position where they
1. 9 Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety checks and
component inspection procedures. lf a fault exists that could compromise safety, then
no electrical supply shall be connected to the circuit until it is satisfactorily dealt with.
lf the fault cannot be corrected immediately but it is necessary to continue operation,
an adequate temporary solution shall be used. This shall be reported to the owner of
the equipment so all parties are advised. lnitial safety checks shall include:
• that capacitors are discharged: this shall be done in a safe manner to avoid
• that there no live electrical components and wiring are exposed while charging,
• that there is continuity of earth bonding.
2
REPAIRS TO SEALED COMPONENTS
2.1 During repairs to sealed components, all electrical supplies shall be
disconnected from the equipment being worked upon prior to any removal
of sealed covers, etc. lf it is absolutely necessary to have an electrical supply to
equipment during servicing, then a permanently operating form of leak detection
shall be located at the most critical point to warn of a potentially hazardous
situation.
2.2 Particular attention shall be paid to the following to ensure that by working
on electrical components, the casing is not altered in such a way that the level
4
92
obstructed;
checked for the presence of refrigerant;
signs that are illegible shall be corrected;
are unlikely to be exposed to any substance which may corrode refrigerant
containing components, unless the components are constructed of materials
which are inherently resistant to being corroded or are suitably protected
against being so corroded.
possibility of sparking;
recovering or purging the system;

Werbung

loading