Note
The fuse block 6 XFTB 001 is not required for PoE power supply.
6.5
Connecting Flashing Warning Beacon Circuits
You can connect up to 4 flashing warning beacon circuits to one beacon control
module.
Flashing warning beacon circuits 1 and 2 are connected to XG2 (OUT 1+2),
Flashing warning beacon circuits 3 and 4 are connected to XG3 (OUT 3+4).
The flashing warning beacons can be connected as line ( chapter 6.5.1,
page 49) or loop ( chapter 6.5.2, page 51).
For the connection of flashing warning beacons, the cable cross-sections for the
cables leading out of the cabinet must be selected based on the type of flashing
warning beacons used and the distance. Observe the INDUSTRONIC Cabling
Guidelines supplied with the system documentation ( GDL-330-001-403).
6.5.1 Line Wiring
1.
Plug the connection cable 8 XCBL 431 into the terminal XG2 (OUT 1+2) or
XG3 (OUT 3+4) ( Fig. 6-5/1) on the beacon control module and connect
the flying leads to the terminal points provided ( chapter 6.3.2, page 47).
4 XBC 001
Input/output DC power supply
XD1
and
The output can be used, for example, for
XD2
connecting or cascading further terminal and
fuse blocks.
F1 to
Fuse for power supply of the beacon control
F6
module and further INTRON-X modules
(max. 6)
F1 = XD3
F4 = XD6
XD3 to
Terminals to connect the power supply of the
beacon control module XBC and further
XD8
INTRON-X modules (max. 6)
UMN-326-030-001 • V02 • DE-EN • 21.08.2023
F2 = XD4
F3 = XD5
F5 = XD7
F6 = XD8