5. Troubleshooting
Module
Error Code
E01:
Overload
Protection
INVERTER
E02:
Over
Temperature
Protection
E03:
Over/Under
Voltage
Protection
E04:
Short Circuit
Protection
Error Code & Troubleshooting
Explanation
When the output power
exceeds 2640W for 30
seconds, the inverter shuts
down, the overload character
flashes, and the buzzer
alarms; when the output
power exceeds 3300W for 10
seconds, the inverter shuts
down, the overload character
flashes, and the buzzer
alarms; the output power
exceeds 4000W for 3 seconds
Seconds, the inverter shuts
down, the overload character
flashes, and the buzzer
alarms.
Cut off the output when the
temperature is above 176°F,
and automatically recover
when the temperature is
below 140°F.
When the voltage of the
inverter is over 140V or below
90V, it will turn off.
ROVER 2000 detects that
there is a short circuit in the
electrical appliance.
Troubleshooting
When the code appears, please cut off
the appliance in time, the error will
disappear immediately.
Please discharge under the suitable
temperature environment (32°F to
104°F).
Step 1: Turn on the power station again
and observe whether the error code is
canceled.
Step 2: Please contact our customer
service if the code still exists.
Step 1: Cut off the output immediately.
Step 2: Turn on the power station again
and observe whether the error code is
canceled.
Step 3: Please contact our customer
service if the code still exists.