Herunterladen Diese Seite drucken

IFM Electronic efector500 PN9 Bedienungsanleitung Seite 15

Combi-drucksensor

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

1. Function and features
• The pressure sensor detects the system pressure,
• shows the current system pressure on its display (indication as
from 1% to 105% of the value of the measuring range),
• and generates 2 output signals according to the set output
configuration.
output 1
hysteresis function / N.O. (Hno)
hysteresis function / N.C. (Hnc)
window function / N.O. (Fno)
window function / N.C. (Fnc)
Applications
Type of pressure: relative pressure
Order no.
PN9xx0/PE9xx0
PN9xx1/PE9xx1
PN9xx2/PE9xx2
PN9xx3/PE9xx3
PN9xx4/PE9xx4
PN9xx6/PE9xx6
PN9xx7/PE9xx7
Avoid static and dynamic overpressure exceeding the given over-
load pressure.
Even if the bursting pressure is exceeded only for a short time
the unit can be destroyed (danger of injuries)!
For gaseous media the application is limited to max. 25 bar.
Indication of the current system pressure as from 1% of the
value of the measuring range. Display "0" does not mean that
the system is free of pressure!
Measuring
range
0 ... 400 bar
0 ... 250 bar
0 ... 100 bar
0 ... 25 bar
0 ... 10 bar
0 ... 2.5 bar
0 ... 1 bar
output 2
analog 0 ... 10 V
Permissible
overl. pressure
600 bar
400 bar
300 bar
100 bar
50 bar
20 bar
10 bar
Bursting
pressure
1000 bar
850 bar
650 bar
350 bar
150 bar
50 bar
30 bar
15

Werbung

loading

Diese Anleitung auch für:

Efector500 pe9