PRIOR MANUFACTURER CONFIGURATION

The unit must be configured from the installer menu in order to function correctly:
Set the indoor unit address to address 1:
1.
Go to menu "17. HMI ADDRESS SET".
EN
2.
Set the parameters to the following values:
17.1 HMI SET = MASTER
17.2 HMI ADDRESS FOR BMS = 1
Set the unit to water supply mode (LWT):
1.
Go to menu "5. TEMP. TYPE SETTING".
2.
Set the parameters to the following values:
5.1 WATER FLOW TEMP = YES
5.2 ROOM TEMP = NON
5.3 DOUBLE ZONE = (NON for 1 circuit, YES for 2 circuits)
3.
Go to menu "6. ROOM THERMOSTAT".
4.
Set the parameters to the following values:
6.1 ROOM THERMOSTAT = NON
Note: Changes must be saved before exiting the menu.