DeviceNet™ Klassen SAI-AU
Number
6,8,10,12
Name
Sensor Type
Data Type
Unsigned Short Integer USINT
Access
Get / Set
Description
Configure Sensor Type of Sensor 1..4
Sensor Type:
0
1
2
3
4
5
6
7
8
9
10
16
Number
7,9,11,13
Name
Sensor Cycle Time
Data Type
Unisgned Short Integer USINT
Access
Get / Set
Description
Configure Cycle Time of Sensor 1..4
Cycle Time:
0
1
2
3
4
5
Number
14,17,20,23
Name
Sensor Connection Type
Data Type
Unsigned Short Integer USINT
Access
Get / Set
134
PT100
PT200
PT500
PT1000
Ni100
Ni120
Ni1000
Resistor 500 Ohm
Resistor 5k Ohm
Potentiometer 100-500 Ohm
Potentiometer 500 – 5k Ohm
No Sensor
50 + 60 Hz supress / slow (620 ms)
50 Hz supress / slow (140 ms)
60 Hz supress / slow (120 ms)
50 + 60 Hz supress / fast (220 ms)
50 Hz supress / fast (60 ms)
60 Hz supress / slow (54 ms)
1105680000/1.0/08.09