Herunterladen Diese Seite drucken

Maico WS 170 R Installationsanleitung Seite 72

Vorschau ausblenden Andere Handbücher für WS 170 R:

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

uk │ 10. Technical data
10. Technical data
Housing dimensions
(W x H x D) in mm
● WS 170 standard unit
● WS 170 comfort unit
● WS 170 bypass unit
Material
Air connections
Condensate drain
Protection class
Degree of protection
G4 outside air filter:
Included with standard unit,
optional with comfort and
bypass unit
G4 exhaust air filter:
Included in all units
F7 pollen filter in comfort
and bypass unit
Permissible ambient
temperature
in installation room
70
595 x 820 x 375
595 x 820 x 375
595 x 820 x 435
Galvanised
sheet steel,
partly powder-
coated
Ø 125 mm
Sleeve with
Ø 28 mm lip
seal, 28x19 mm
reducer for
3/4" hose
1
IP 00
WSG 170
air filter,
class G4
WSG 170
air filter,
class G4
WSF170,
pollen filter,
class F7
+10 ... +40 °C
Permissible moisture in
installation room (at 20 °C)
● Standard unit
● Comfort unit
● Bypass unit
Permitted outside air
temperature
Degree of heat provision
Rated voltage
power frequency
Ventilation levels
(factory setting):
Humidity protection
ventilation (interval
operation)
● Reduced ventilation
● Nominal ventilation
● Intensive ventilation
Power consumption (unit)
at 100 Pa Counter
pressure per duct
● 60 m³/h
● 90 m³/h
● 120 m³/h
Weight
● Standard unit
● Comfort unit
● Bypass unit
50 % RH
70 % RH
70 % RH
-15 ... +60 °C
up to 94 %
230 V AC
50 Hz / 60 Hz
approx. 57 %
of reduced
ventilation
60 m³/h
90 m³/h
120 m³/h
24 W
35 W
50 W
38 kg
43 kg
47 kg

Werbung

loading