Herunterladen Inhalt Inhalt Diese Seite drucken

Victron energy BLUE POWER MultiPlus 12 500 20 Anleitung Seite 17

Vorschau ausblenden Andere Handbücher für BLUE POWER MultiPlus 12 500 20:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 67
5.3 Configuration by computer
All settings can be changed by means of a computer.
Some settings can be changed with DIP switches (see Section 5.2).
For changing settings with the computer, the following is required:
- VEConfigure3 software: can be downloaded free of charge at www.victronenergy.com.
- A MK3-USB (VE.Bus to USB) interface, and a RJ45 UTP cable.
Alternatively, the Interface MK2.2b (VE.Bus to RS232) and a RJ45 UTP cable can be used.
5.4 Configuration with DIP switches
Some settings can be changed with DIP switches.
Procedure:
a) Turn the Multi on, preferably without load and without AC voltage on the input. The Multi
will then operate in inverter mode.
b) Set the DIP switches as required.
c) Store the settings by moving DIP switch 6 to 'on' and back to 'off'.
5.4.1. DIP switch 1
Default setting: to operate the product with the 'On/Off/Charger Only' switch
ds 1: 'off'
Setting for operation with a 3 position remote switch or the Digital Multi Control panel:
ds 1: 'on'
The 3 position switch must be wired to terminal L, see appendix A.
Only one remote control can be connected, i.e. either a switch or a Digital Multi Control
panel.
17

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis