Quick guide PTC thermistor relay MSR820V
1 Application and short description
ZIEHL PTC thermistor tripping devices protect motors, transformers, machines and systems against thermal overload.
Together with ZIEHL PTC thermistor temperature sensors type MINIKA®, response values between 60°C and 180°C can be
realized.
The MSR820V monitors up to 8 PTC thermistor circuits. The individual circuits can be activated or deactivated during
operation.
2 Technical data
Rated supply voltage Us:
Tolerance
Power Consumption
PTC thermistor connection:
Number
Shutdown value
Reset value
Short-circuit detection
Terminal voltage
Sensor current
Power consumption
Relay output:
Switching voltage
Switching current
Switching power (resistive
load)
Nominal operating current Ie
for changers
Recommended back-up fuse
Mechanical contact life
Electrical contact life
Housing:
Dimensions (w x h x d)
Protection class
Weight
MSR820V
12400-0750-02
Mains Monitoring
Digital Panelmeters MINIPAN®
AC/DC 24 – 240V, 0/50/60Hz
DC 20,4–297V / AC 20–264V
< 1 W, < 3 VA
PTC sensor according to DIN 44081/82
8 sensor circuits x 1...6 PTC thermistors
(250Ω) in series
3.3kΩ...4kΩ, typical 3.65kΩ
1.5kΩ...1.65kΩ, typical 1.6kΩ
On: approx. 20 Ω
≤ 2.0V at R ≤ 3.65kΩ, ≤ 3.3V at R = ∞
≤ 1.25mA
≤ 2mW
2 x 1 Change-over contact (CO) (Bistable
relays)
max. AC 440 V, max. DC 230 V
max. 8 A
max. 2000 VA
max. 240 W at DC 30 V
AC15 Ie = 3 A
DC13 Ie = 0,2 A
max. 4 A
107 operations
Resistive 1 x 105 AC
Resistive 5 x 104 DC
Design V4, switchgear mounting
70 x 90 x 58 mm
IP30 (housing), IP20 (terminal)
approx. 180g
Switching Relays and Controls
You can get further information and help via the
or search for
MSR820V
Datasheets, Operating Manuals and quick guides, Connection
Plans, CAD-Data, copious FAQ, Certificates.
3 Connection Plan
BR1: Restart interlock switched off
Seite 3 / 4
ZIEHL industrie – elektronik GmbH + Co KG
Daimlerstr.13, 74523 Schwäbisch Hall, Germany
+ 49 791 504-0,
info@ziehl.de,
Measuring Transducers
Grid- and Plant Protection
updated: 2023-07-05 / dr
at ziehl.de.
www.ziehl.deAA