Maintenance
a) The machine is designed and built to guarantee continuous
operation; however, the life of its components depends on the
maintenance performed;
b) when requesting assistance or spare parts, identify the ma-
chine (model and serial number) by reading the data plate lo-
cated on the unit.

6.1 General instructions

!
Before any maintenance, make sure:
• the pneumatic circuit is no longer pressurized;
• the dryer is disconnected from the main power supply
Y
.
Always use the Manufacturer's original spare parts: oth-
erwise the Manufacturer is relieved of all liability regarding ma-
chine malfunctioning
Y
In case of refrigerant leakage, contact qualifi ed and author-
ized personnel.
Y
The Schrader valve must only be used in case of machine
malfunction: otherwise any damage caused by incorrect refriger-
ant charging will not be covered by the warranty.
6.2 Refrigerant.
Charging: any damage caused by incorrect refrigerant replace-
ment carried out by unauthorized personnel will not be covered
Z
by the warranty.
Y
The equipment contains fl uorinated greenhouse gases.
At normal temperature and pressure, the R513A refrigerant is a
colourless gas classifi ed in SAFETY GROUP A1 - EN378 (group
2 fl uid according to Directive PED 2014/68/EU)
GWP (Global Warming Potential) = 573.
!
In case of refrigerant leakage, ventilate the room.
SPS004-SPS100
6.3 Preventive Maintenance Programme
To guarantee lasting maximum dryer effi ciency and reliability
Maintenance
Maintenance Interval
Activity Description
(standard operating condi-
Activity
Check
Service
Check POWER ON indicator is
lit.
Check control panel indicators.
Check condensate drain.
Clean condenser fi ns.
Check electrical absorption.
Depressurize the dryer. Com-
plete drain maintenance.
Depressurize the dryer. Replace
pre- and post-fi lter elements.
The following are available (see par. 8.4):
a) compressor kits;
b) fan kits;
c) automatic expansion valve kits;
d) individual spare parts.
6.4 Dismantling
The refrigerant and the lubricating oil contained in the circuit
must be recovered in conformity with current local environmen-
tal regulations.
The refrigerant fl uid is recovered before fi nal scrapping of the
)
tions
equipment ((EU) No. 517/2014 art.8).
%
structural work
exchanger
pipes
drain
exchanger insulation
pipe insulation
compressor
condenser
refrigerant
valves
electrical cables
Equipment containing electrical components
must be disposed separately collected with
electrical and electronic waste according to
local and currently legislation.
4 / 6
Z
Recycling Disposal
steel/epoxy-polyester resins
aluminium
aluminium/copper
polyamide
EPS (sintered polystyrene)
synthetic rubber
steel/copper/aluminium/oil
steel/copper/aluminium
R513A
brass
copper/PVC