Connection option 4:
Ventilation unit + Room air control +
CO
/ VOC / RFS sensor. Refer also to the
2
wiring diagram in the appendix.
A
Ventilation unit RB 300 or RB 400
A2
Control circuit board: Jumper 8 bridged
= factory setting. Jumper 10
bridged  sensor is recognised.
B
Room air control RB-D1-ZF4
B1
Room air control RB-ZF4
(option to RB-D1-ZF4)
CO2
CO
-Sensor SKD, see accessories
2
VOC
Air quality controller EAQ 10/2
RFS
Humidity control
W1
230 VAC connecting cable
W2
Screened control cable (to be supplied
by customer) for RB-D1-ZF4 control
W2´
Control cable for room air control RB-
ZF4 (to be supplied by the customer)
W4
Connecting cable for an external CO
or VOC sensor (to be supplied by the
customer). External diameter 3,2 to
6,5 mm, z. B. LIYY 3 x 0,5 mm².
Connection to control circuit board A2
at terminals "CO2" and "OT". Set
jumper 10 (CO2) to release the
feature, see figure.
Connection of a CO
controller for the demand-driven supply of
fresh air. The ventilation unit only reacts to
sensor if ventilation level 2 (nominal
ventilation) is selected at the room air control.
VOC/RFS
Permitted connection
● 1x CO
1x humidity control RFS.
● RB-D1-ZF4 (B) not combinable with a
RB-ZF4 (B1).
● Connection of a CO
only permitted with a room air control.
● Damage of device: Never combine an
RFS with a CO
CO
< 900 ppm
< 25 % r. h.
> 1000 ppm
> 50 % r. h.
> 1100 ppm
2
> 75 % r. h.
< 1000 ppm
< 50 % r. h.
ppm: parts per million / r. h.: relative humidity
, air quality or humidity
2
Jumper 10 is set on the
i
control circuit board A2.
-sensor or 1x VOC-sensor or
2
2
-/VOC-sensor.
2
sensor switching points
2
Ventilation unit switches to
ventilation level 1. Ventilation
level 2 is shown at the room
air control.
Ventilation unit switches from
ventilation level 1 to ventilation
level 2.
Ventilation unit switches to
ventilation level 3. Ventilation
level 2 is shown at the room
air control.
Ventilation unit switches from
ventilation level 3 to ventilation
level 2.
/VOC/RFS-sensor
81