Operation and Maintenance Documentation of air curtains GUARD PRO v202301
The Multi 6 control box allows to connect and control up to 6x GUARD PRO 200 and 6x servomotors. The control of the unit
motors is via Panel COMFORT New or INTELLIGENT, there is a possibility to connect DOORSTOP switch to it. The thermostat
has a primary function when connected to the unit with the Doorswitch. In order to connect more than 6 air curtains there is a
possibility of connecting up to 10 Multi 6 controls in serial. To do so in to remove the DS-N jumper in the first Multi 6 box and
install DS-N jumper in all the other boxes.
Power supply for PTC heaters are 3x400V/50Hz
For GUARDPRO 150E use wire min. 5x6mm
For GUARDPRO 200E use wire min. 5x6mm
8.
HYDRONIC CONNECTION
Water connections are located at the back of the unit on the right side. Connections should allow access for service and
maintenance therefore on both nozzles the shut-off valves should be installed. The order of connecting inlet/outlet pipes does
not affect the operation of the exchanger.
9.

OPERATION AND MAINTENANCE

The engine and fan used in the GUARD PRO air curtains are maintenance-free devices but regular check-ups are advised,
especially motor and bearing (the fan's rotor should rotate freely, free from any axial and radial throws/run-outs and undesired
knocks/rattles.
The heat exchanger requires systematical cleaning of all dirt/impurities. Before the start of the heating period, the heat
exchanger is advised to be cleaned with compressed air directed to the air outlets; there is no need for dismantling the device.
Pay special attention when cleaning the exchanger's fin due to the high possibility of damaging them. If the fin is bent, use a
special tool. If the device has not been used for a longer period, unplug it before the next use.
The heat exchanger is not equipped with any anti-freeze protection device. The heat exchanger may be damaged if the room
temperature goes below 0°C.
If the device is to operate in a room where the temperature goes below 0°C, anti-freeze liquid must be added to
the water circulation/system. Anti-freeze liquid must be appropriate for the material the exchanger is made of
(copper), as well as other elements of the hydraulic system/circulation. The liquid must be diluted with water
accordingly to the manufacturer's recommendation.
Any repair and maintenance work must be conducted with the power off and the heat input disconnected.
Only suitably qualified staff well acquainted with the safety regulations concerning handling an electrical
device must be employed when the device is being installed, started and operated
In the event of a coolant leak, when the water system is under pressure, any repairs of the leakage are
strictly prohibited.
Any repairs to the device must be conducted only if the device is disconnected from the power supply.
If the device being operated gives a metallic clatter, or vibration or the level of noise is increasing, check if the
mounting of the fan has not become loose – in case of any problems contact the installer of the device or the
SONNIGER Authorized Service immediately
NOTICE !
2
, fuse B25
2
, fuse C32
NOTICE!