Connecting-up
X103 - 10 V voltage
output, SCom1,
SCom2
X300 - Serial
interface
5
Switch settings
7-12
Downloaded from
www.Manualslib.com
The following connections are provided on the control terminal strip:
♦ 10 V aux. voltage (max. 5 mA) for the supply of external
potentiometers
♦ 2 serial interfaces SCom1 and SCom2 (USS / RS485)
Terminal
23
24
25
26
27
28
Connectable cross-section: 0.14 mm
The terminals 23 and 24 are short-circuit proof.
Terminal 23 is at the top when installed.
Table 7-6
Either an OP1S or a PC can be connected up via the 9-pole SUB D
socket.
The 9-pole SUB D socket is internally coupled with the USS bus, with
the result that it is possible to exchange data with further converters
and inverters which are linked via the USS bus.
Pin
1
2
1
3
4
5
9
6
6
7
8
9
M_RS232/485
Table 7-7
S1
open
closed
S2
open
closed
manuals search engine
Designation
+10 V supply for ext.
P10 V
N10 V
-10 V supply for ext.
RS485 P (SCom2) USS bus connection SCom2
RS485 N (SCom2) USS bus connection SCom2
RS485 P (SCom1) USS bus connection SCom1
RS485 N (SCom1) USS bus connection SCom1
Control terminal strip X103
Name
Meaning
n.c.
Not connected
RS232 RxD
Receive data via RS232
RS485 P
Data via RS485
Boot
Control signal for software
update
M5V
Reference potential to P5V
P5V
5 V aux. voltage supply
RS232 TxD
Transmit data via RS232
RS485 N
Data via RS485
Digital ground (choked)
Serial interface X300
Switch
SCom1 (X300): Bus terminating resistor
Resistor open
Resistor closed
SCom2 (X101/10,11): Bus terminating resistor
Resistor open
Resistor closed
Operating Instructions
Meaning
Range
+10 V ± 1.3 %,
potentiometer
Imax = 5 mA
-10 V ± 1.3 %,
potentiometer
Imax = 5 mA
RS485
RS485
RS485
RS485
2
2
to 1.5 mm
(AWG 16)
Range
RS232
RS485
Digital signal, low
active
0 V
+5 V, Imax = 200 mA
RS232
RS485
Meaning
6SE7087-6KN50