Description

The Access Point unit (AP) is used for controlling one
door environment. It uses a common Internet/Intranet
connection (Ethernet) and connects to a PC with the
Aliro software (server). The AP gets its configuration
from the host and will take all decisions locally. The AP
also sends the events to the server.
Normally, the AP is connected to a reader which
enables users to access areas according to access
rights.

Safety

Read the general safety precautions before installing/-
configuring/operating the device.
Follow all warnings and instructions marked on the
l
device.
Keep this document for reference purposes.
l
Please take into account any additional country-
l
specific, local laws, safety standards or regulations
concerning installation, operation and disposal of
the product.
Refer to a qualified electrician for installation.
l

Standards and guidelines

European directives
Siemens Security Products hereby declares that this
product is in compliance with the essential requirements
and other relevant provisions of Directive 2004/108/EC
on Electromagnetic Compatibility (EMC).
The EC Declaration of Conformity is available from
your Siemens sales office or:
Siemens AB, Englundavägen 7, SE-171 24 Solna
Sweden

Details of ordering

Type
Item Number
AP01P
S54503-C101-A100 Aliro Access Point, 1
Siemens AB

ENGLISH

Description
door

Technical data

Supply voltage (nom.*)
Absolute voltage
ratings**
Current consumption
Battery type
Reader interface
Inputs
Outputs
Temperature range
Humidity
Environmental class
Dimensions (H x W x D)
* Nominal voltage has margins for transformer tolerances, mains
supply variations and interruptions.
** Absolute voltage has no margins and should be used for
guidance only.
*** Full on represents:
500mA load on high-speed USB connector
l
100mA load on full-speed USB connector
l
No readers connected
l
Relays activated
l
RS485 communication on all ports with EOL resistors
l
Micro-SD Memory card installed
l
12-24 Vnom +/- 10% 1Vpp
ripple
9.5 VDC-29.5 VDC
The AP Power Supply
input must be protected by
a fuse (2A).
Without reader
Idle:
12V DC: 200 mA
24V DC: 125 mA
Full on:***
12V DC: 600mA
24V DC: 400 mA
CR2032
Two (RS485, Clock-Data
or Wiegand) plus Power
out.
700 mA (jumper in Vin
position)
200 mA (jumper in 12V
position)
Four general inputs.
Two relay outputs. Max
30VDC, 2A. One bi-stable,
one mono-stable.
Four Open-collector
outputs, max load 0.5A
One power supply output
with Vin, max load 2A.
-40 to +55°C
25°C @ 80% -> 55°C @
93% (III, IEC 60839-11-1)
II, IEC 60839-11-1
156 x 201 x 53 mm
2014-09-11
7