Quick Setup: steps 1 to 9
Factory settings are marked by an asterisk (*) in the tables.
Note:
1. Select language (P010: Language)
Numeric/None
0
*
English
1
German
Value
2
French
3
Spanish
4
2. Set P001: Operation (measurement mode)
Notes:
• Setting P001 resets Span (P007), unless Span has previously been set to a different value.
• Changing P001 may reset Output Function (P201): this applies to HART only.
Level returns distance to material level referenced from Empty (process empty level). The
1 *
reading is returned in volumetric units if parameters 050 to 055 are set to enable this.
Value
2
Space returns distance to material level referenced from Span (process full level).
3
Distance returns distance to material level from reference point.
mA Output with Level, Space, and Distance operation
Level
(P001 = 1)
Span
P006
P007
Empty
3. Set P003: Measurement Response
1
*
slow
Value
2
medium
3
fast
Set P003 to a measurement response speed
just faster than the maximum filling or
emptying rate (whichever is greater).
Page EN-16
SITRANS LR200 (HART) – QUICK START MANUAL
ENGLISH
P000
LOCK
P001
OPERATION
P003
MEAS RESP
P004
ANTENNA
P005
UNITS
P006
EMPTY
P007
SPAN
P010
LANGUAGE
Space
(P001 = 2)
(20 mA)
Span
100%
Level
Empty
0%
(4 mA)
(P004 - view only)
0.1m/minute
1m/minute
Value
10m/minute
DEUTSCH
FRANÇAIS
VERRIEGELG
VERROUIL
BETRIEB
FONCTIONMT
REAKTIONSZ
TEMPS REP .
ANTENNE
ANTENNE
EINHEIT
UNITES
MESSBER.
VIDE
MESSSPANNE
PLAGE
SPRACHE
LANGUE
Distance
(P001 = 3)
(4 mA)
0%
Space
100%
(20 mA)
240 *
rod antenna
241
rod + 50 mm PTFE extension
242
rod + 100 mm PTFE extension
ESPAÑOL
BLOQUEO
FUNCIONAM.
TIEMPO R.
ANTENA
UNIDADES
VACIO
RANGO
IDIOMA
(4 mA)
0%
Span
Distance
Empty
100%
(20 mA)