Herunterladen Diese Seite drucken
Honeywell NOTIFIER NFX-Serie Installations- Und Wartungsanleitung
Honeywell NOTIFIER NFX-Serie Installations- Und Wartungsanleitung

Honeywell NOTIFIER NFX-Serie Installations- Und Wartungsanleitung

Thermomelder

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

102 mm
B501AP
INSTALLATION AND MAINTENANCE INSTRUCTIONS
ENGLISH
FOR THE NFX/NFXI THERMAL FIRE SENSORS
GENERAL DESCRIPTION
The NFX/NFXI intelligent thermal sensors are plug-in type fire sensors that use a
single thermistor sensing circuit to provide early warning of developing fires, together
with addressable communication with the fire panel.
The NFX-TDIFF/NFXI-TDIFF provides fixed 58
temperature sensing (Category A1R).
The NFX-TFIX58/NFXI-TFIX58 provides fixed 58
The NFX-TFIX78/NFXI-TFIX78 provides fixed 78
These sensors are designed for open area protection and must only be connected to
fire panels that use a compatible proprietary communication protocol for monitoring
and control.
The NFXI sensors contain an isolator, if installing this version check the panel
documentation for details of how many isolators can be used on a loop.
Two LEDs on each sensor light to provide a local 360
of LEDs are dependent on panel). Remote LED indicator capability is available as an
optional accessory wired to the standard base terminals (again dependent on panel).
SPECIFICATIONS
Operating Voltage Range:
Max. Standby Current (no comm.): 160 µA @24 V and 25
(comm. LED blink enabled - 5 sec) 300 µA @24 V and 25
(Read 16 sec. LED blink 8 sec)
Max. Alarm Current (LED on):
Operating Humidity Range:
Isolator Characteristics (NFXI Versions Only): see S00-7300
These sensors have been Independently tested and certified, see CE table.
EN 54-5: 2017 + A1: 2018 states that Class A1 has a maximum application temperature
of 50
C, Class B has a maximum application temperature of 65
o
WIRING GUIDE
Refer to the installation instructions supplied with the plug-in sensor bases for wiring
details. All bases are provided with terminals for power and an optional Remote Indicator.
Note 1: All wiring must conform to applicable local and national codes and regulations.
Note 2: Verify that all sensor bases are installed and that polarity of the wiring is correct
at each base.
Disconnect loop power before installing sensors. Notify proper authorities.
SENSOR INSTALLATION
1. Set the sensor address (see figure 1) by turning the two rotary switches on the un-
derside of the sensor, selecting a number between 01 and 159. (Note: The number of
addresses available will be dependent on panel capability, check the panel documenta-
tion for information on this). Record the address on the label attached to the base.
Figure 1: Rotary Address Switches
X 10
2. Insert the sensor into the base and rotate it clockwise until it locks into place.
3. After all the sensors have been installed, apply power to the system.
4. Test the sensor as described under TESTING.
5. Reset the sensor by communication command from the panel.
Tamper-Resistance.
These sensors includes a feature that, when activated, prevents removal of the sensor
from the base without the use of a tool. Refer to the installation instructions for the
sensor base for details of how to use this feature.
N200-203-00
Honeywell Building Technologies, Building 5 Carlton Park, King Edward Avenue, Narborough, Leicester LE19 3EQ
NFX(I)-TDIFF NFX(I)-TFIX58 NFX(I)-TFIX78
80°C
-30°C
C and rate-of-rise (10
o
C temperature sensing (Category A1S).
o
C high temperature sensing (Category BS).
o
visible sensor indication (operation
o
see S00-7300
C
o
C
o
190 µA @24 V and 25
C
o
add 50 µA for NFXI isolated models
3.5 mA @ 24 V and 25
C
o
10% to 93% Relative Humidity, Non-Condensing
C.
o
WARNING
X 1
DOP-IFD150 NFX-TDIFF
DOP-IFD151 NFXI-TDIFF
0832
DOP-IFD146 NFX-TFIX58
22
DOP-IFD147 NFXI-TFIX58 EN 54-5: 2017 + A1: 2018 Category A1S, EN 54-17: 2005
DOP-IFD148 NFX-TFIX78
0786
DOP-IFD149 NFXI-TFIX78 EN 54-5: 2017 + A1: 2018 Category BS, EN 54-17: 2005
09
Notifier Fire Systems by Honeywell, Pittway Tecnologica S.r.l, Via Caboto 19/3, 34147 Trieste, Italy
88 g
Dust covers help to protect units during shipping and when first installed.
They are not intended to provide complete protection against contamination
therefore sensors should be removed before construction, major re-decora-
tion or other dust producing work is started. Dust covers must be removed
C/minute)
o
MAINTENANCE
Before cleaning, disable the system to prevent unwanted alarms:
1. Remove the sensor to be cleaned from the system.
2 Use a vacuum cleaner and/or clean, compressed air to remove dust and debris from
the thermistor and sensor cover.
3. Replace the sensor into the base.
4. When all sensors have been cleaned, restore power to the loop and test the sensor(s)
as described under TESTING.
TESTING
Sensors must be tested after installation and following periodic maintenance. Disable
the zone or system undergoing maintenance to prevent unwanted alarms.
Test the sensors as follows:
Magnet Method
1. Test the sensor by positioning the test magnet (model M02-24-optional) against the
sensor body approximately 2 cm from LED 1, indicated by a mark on the sensor
cover as shown in figure 2.
2. Both LED's on the sensor should latch into alarm within 30 seconds, activating the
control panel.
Figure 2: Test Magnet Position
Control Panel Method
1. Test the sensitivity from the system control panel.
Direct Heat Method (Hair dryer of 1000-1500 watts).
1. Direct the heat toward the sensor from its side. Hold the heat source about 15 cm
away to prevent damage to the cover during testing.
2. The LEDs on the sensor should light when the temperature at the sensor reaches
58°C/78°C (dependent on the model being tested).
3. Reset the sensor at the system control panel.
After completion of the test notify the proper authorities that the system is operational.
Fire sensors must be used in conjunction with compatible equipment.
Heat sensors are designed to protect property, not life. They do not provide early
warning of fire and cannot detect smoke, gas, combustion particles or flame.
Heat sensors do not always detect fires because the fire may be a slow smouldering,
low-heat type (producing smoke) or because they may not be near where the fire occurs,
or because the heat of the fire may bypass them. Consideration must be made of the
environment when selecting heat sensors.
Fire sensors cannot last forever. Fire sensors contain electronic parts. Even though
sensors are made to last over 10 years, any of these parts could fail at any time.
Therefore, test your fire detection system at least semi-annually. Taking care of the fire
detection system you have installed will significantly reduce your product liability risks.
EN 54-5: 2017 + A1: 2018 Category A1R
EN 54-5: 2017 + A1: 2018 Category A1R, EN 54-17: 2005
EN 54-5: 2017 + A1: 2018 Category A1S
EN 54-5: 2017 + A1: 2018 Category BS
CAUTION
before system can be made operational.
Test
Magnet
Mark on Cover
LED 2
WARNING
LIMITATIONS OF THERMAL SENSORS
LED 1
I56-3391-007

Werbung

loading

Inhaltszusammenfassung für Honeywell NOTIFIER NFX-Serie

  • Seite 1 EN 54-5: 2017 + A1: 2018 Category BS 0786 B501AP DOP-IFD149 NFXI-TFIX78 EN 54-5: 2017 + A1: 2018 Category BS, EN 54-17: 2005 80°C Notifier Fire Systems by Honeywell, Pittway Tecnologica S.r.l, Via Caboto 19/3, 34147 Trieste, Italy 88 g -30°C INSTALLATION AND MAINTENANCE INSTRUCTIONS CAUTION...
  • Seite 2 0786 B501AP DOP-IFD149 NFXI-TFIX78 EN 54-5: 2017 + A1: 2018 Category BS, EN 54-17: 2005 80°C Notifier Fire Systems by Honeywell, Pittway Tecnologica S.r.l, Via Caboto 19/3, 34147 Trieste, Italy 88 g -30°C ISTRUZIONI DI INSTALLAZIONE E MANUTENZIONE DI Sistema antimanomissione...
  • Seite 3 EN 54-5: 2017 + A1: 2018 Category BS 0786 B501AP DOP-IFD149 NFXI-TFIX78 EN 54-5: 2017 + A1: 2018 Category BS, EN 54-17: 2005 80°C Notifier Fire Systems by Honeywell, Pittway Tecnologica S.r.l, Via Caboto 19/3, 34147 Trieste, Italy 88 g -30°C INSTRUCCIONES DE INSTALACIÓN Y PRECAUCIÓN MANTENIMIENTO DE LOS SENSORES DE INCENDIO ESPAÑOL...
  • Seite 4 0786 B501AP DOP-IFD149 NFXI-TFIX78 EN 54-5: 2017 + A1: 2018 Category BS, EN 54-17: 2005 80°C Notifier Fire Systems by Honeywell, Pittway Tecnologica S.r.l, Via Caboto 19/3, 34147 Trieste, Italy 88 g -30°C INSTALLATIONS- UND WARTUNGSANLEITUNG FÜR Sabotageschutz / Entnahmesicherung DEUTSCH Der Meldersockel verfügt über eine Entnahmesicherung die das Entfernen des...

Diese Anleitung auch für:

Notifier nfxi-serieNotifier nfx-tdifNotifier nfxi-tdiffNotifier nfx-tfix58Notifier nfxi-tfix58Notifier nfx-tfix78 ... Alle anzeigen