4. Mounting
The universal isolators are mounted on standard TS 35 rails.
5. Electrical connection
Terminal assignments
1 Input +
2 Input -
3 Input +
4 Input -
5 Output +
6 Output -
7 Power supply
8 Power supply
Wire cross-section max. 2,5 mm2
Multi-wire connection max. 1 mm2
(two wires with same cross-section)
Warning!
Do not operate inputs for current and voltage simultaneously! For applications
with high working voltages, take precautions to prevent accidental contact
and make sure that there is sufficient distance or insolation between adjacent
devices!
5.1 Power supply
22 to 230 V AC/DC ±10 %, approx. 1 W, AC 48 to 62 Hz
16
current
current
voltage
voltage