Herunterladen Inhalt Inhalt Diese Seite drucken
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 3
ENG | Instruction Manual
MOUNTING
The valve unit is mounted upright either on the right- or left-hand side
of the heating boiler. The thermometers are pressed onto the front
side of the unit.
For a trouble free system the piping work must be done without air pock-
ets. If this is not possible the system must be fitted with air vents.
Several boilers have integrated thermostats for pump control. If not,
a flue gas thermostat must be installed. The circulation pump should
start at the same time as the firing. The pump should stop soon after
the fire has gone out to let the remaining hot water in the boiler self-
circulate to the storage tank.
DIMENSIONING
Pipe dimensioning between heating boiler and storage tank:
LK 810 ThermoMat G loading unit with Rp 1" ball valves.
For heating boilers up to 45 kW ..... DN 25
LK 810 ThermoMat G loading unit with 28 mm ball valves.
For heating boilers up to 45 kW .... DN 28
LK 810 ThermoMat G loading unit with Rp 1¼" ball valves.
For heating boilers up to 90 kW .... DN 32

CIRCULATING PUMP

Three pump positions are available depending on boiler capacity.
It is to be noted that the maximum capacity of a boiler may be
higher than its nominal capacity.
REPLACING THERMOSTATIC ELEMENTS
Turn off the pump
Close the three ball valves
Screw off the upper ball valve from the loading unit
Loosen the two remaining ball valves
Tilt the loading unit forwards
Unscrew the element housing
Replace the thermostatic element
After replacing the element, open the three ball valves and start
the pump. Check that there is no air in the system.
2
FUNCTION OF THE BACKFLOW PREVENTER
LK 810 ThermoMat G loading unit has, depending on model, a back-
flow preventer which automatically opens for selfcirculation when the
pump stops. The backflow preventer has the following functions:
1.
After the fire has gone out and the circulating pump has stop-
ped the remaining hot water will selfcirculate to the storage
tank.
2.
In case of power failure the hot water will self-circulate to the
tank.
3.
It prevents backflow from storage tank to heating boiler.
The function of the backflow preventer can, if needed, be blocked. The
backflow preventer is then replaced by a plug LKA art.no: 187 022.
See page 14-15, part 13.
FUNCTION
www.lkarmatur.com
1. HEAT UP PHASE
The water circulates between boiler and
loading unit while the temperature of the
boiler is rising.
2. LOADING PHASE
The thermostatic element starts to open and
allows return water from the storage tank to
be mixed with supply water before it returns
to the boiler. The return temperature to the
boiler is kept constant.
3. END PHASE
The thermostatic element is fully open and
the bypass is closed. This results in an
optimal transfer of heat from the boiler and
the storage tank is filled with supply water.
4. SELF CIRCULATION WITH CHECK VALVE
Self-circulation will be obtained as soon
as the fire has gone out and the circulating
pump has stopped. The remaining hot
water is loaded to the storage tank. In case
of power failure or pump breakdown the
check valve automatically opens to allow
self-circulation. The check valve also stops
recirculation from storage tank to boiler.

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis