PV-Terminals
Battery Terminals
Load Terminals
USB output interface
Mounting Hole ø4.5mm
4. Wiring
Connect the system in the order of Battery Load PV array and disconnect the system in the
reverse order (see figure 2).
NOTE: While wiring the controller do not close the circuit breaker or fuse and make sure that the
leads of „+" and „-" poles are connected correctly.
NOTE: A fuse which current is 1.25 to 2 times the rated current of the controller must be instal-
led on the battery side with a distance from the battery not greater than 150 mm.
NOTE: If an inverter is to be connected to the system, connect the inverter directly to the battery,
not to the load side of the controller.
Mini Anderson Input
Button for setting the consumer
and to set the battery type
Battery status LEd indicator
Load status LEd indicator
Charging status LEd indicator
USB Output
DC5V 1.2A
Figure 2
17