Marking
TECHNICAL
Certification
DATA
Product standard
Electrical:
Operating voltage U
Rated current I
Current switch-off
(in case of overload or short circuit)
Switch-off times for
electronic switch-off
Capacitive loads
Inductive loads
Mechanical:
Number of channels
Width
Height
Depth
Input terminals (optional)
Output terminals
Terminal type
Terminal capacity
Communication port
Terminal type
Terminal capacity
Busbar
Assembly
Status LED
Slide switch
Remote signaling output
Remote signaling input
Eaton Industries (Austria) GmbH, Eugenia 1, A-3943 Schrems
www.eaton.eu/documentation
B
N
CE
UL508 + UL2367 (section 10 and 12) in progress
Applicable sequences of:
EN60947-1, EN60947-5-1, EN61009-1,
EN61131-2 and EN61000-4-2
Details acc. to Werksnorm WN 1008
24 DC (16....30 V DC)
Fix; 2, 4, 6, 8, 10, 13, 16A
Typically 1.2 x I
with active current limitation
N
see time / current table
Up to 20,000 μF
Up to 13A
1
17.5 (1 HP)
92.5mm
119.2mm
3 x LINE (+) and 3 x GND (-)
3 x LOAD (+) and 3 x GND (-)
Push-in terminals
2.5mm² (flexible with ferrule)
4mm² (rigid)
2 x remote signaling output (internally linked)
2 x remote signaling input (internally linked)
1x GND
Push-in terminals
0.75mm² (flexible with ferrule)
1.5mm² (rigid)
LINE (+) and GND (-); max. 80A
In different lengths up to 1m
Snap-fit onto the TH35 mounting rail (EN 60715)
Two-colored; Green = OK; Red = Tripped
Off = channel not in operation
On/Off/Reset
Tripped; via communication port
(in accordance with IEC 61131-2), class: 0.1A;
Type1/Type2 and Type3 digital inputs
Max. 30 PXS24V units can be connected simultane-
ously.
External signal sources up to 0.2A at 24V. (EATON
RMQ series,...)
On/Off/Reset; via communication port
6
MA-PXS24_Standard.docx/10.2017a
150501507/IL019188ZU