Parameter table:
Code
A
Water inlet temperature
b
Water outlet temperature
c
Ambient temperature
d
Temperature set
E
Automatic defrost activation time
F
Maximum defrosting time
H
Set temperature difference for the restart
J
Automatic restart
O
Frost protection - low air temperature
P
Evaporator temperature for entry into defrost mode
U
Evaporator temperature to exit defrost mode
t
Reserved - do not change

6. Maintenance

ATTENTION: Before performing any maintenance tasks, disconnect the electrical device from the
power source by pulling the plug out of the socket outlet.
Do not use aggressive solvents or cleaning agents.
Do not dispose of pool water containing chemicals (e.g. chlorine) on lawns or plants.
The evaporator on the back of the heat pump must be cleaned carefully with a ho over and a soft brush
attachment.
Note: All types of repairs must be carried out by qualified personnel.
Annual maintenance:
Carry out security checks.
Check the integrity of the electrical wiring.
Check the earth connections.
Your heat pump is designed to work even in rainy weather and is protected from frost by specially developed
anti-frost technology. However, it is not recommended to leave them outdoors for long periods (e.g. over
winter). After draining the pool, store the heat pump in a dry place for the winter.
Help in case of faults:
Code
Fault
Fault in the water inlet
P1
temperature sensor
Fault in the evaporator
P3
temperature sensor
Fault of the external
P5
temperature sensor
P7
Freeze protection
E3
Flow sensor fault
Negative pressure
E6
protection
16
Description
Possible cause
Sensor poorly connected
Sensor defective
Defective control panel
Same causes as P1
Protection is activated when the
ambient temperature is too low
Not enough water in the heat
exchanger
Defective flow sensor
Defective control panel
Insufficient refrigerant gas
7
Factory setting
Current data
Current data
Current data
40 min
30 min
Reserved
Remedy
Reconnect sensor
Replace sensor
Replace control panel
Same causes as P1
No input is required
Review the operation of your water circuit
Replace flow sensor
Replace control panel
Refill refrigerant gas
27 °C
3 °C
1
8 °C
-3 °C
20 °C