SW2: Pin 7
Comm:
Baud Rate 19200 (OFF)
Use Register 27 (ON )
Register Name
R/W
1
Run Command
R/W
2
Speed Reference
R/W
3
Operational Status
R
4
Light Control
R/W
5
External Temperature
R
6
Last fault code
R
7
Second last fault
R
8
Third last fault
R
9
Fourth last fault
R
10
Fifth last fault
R
11
Firmware Version
R
12
Operating Hours
R
13
Motor RPM
R
14
Voltage, DC Bus
R
15
Voltage, Output RMS
R
16
Current, Motor RMS
R
17
Temperature, Motor
R
18
Temperature, Transistor
R
19
Temperature, Ambient
R
20
Thermal Speed Derate
R
21
Communication Errors
R
22
--spare--
R
23
-- spare --
R
24
-- spare --
R
25
-- spare --
R
26
KEEP ALIVE (WatchDog)
R/W
27
MODBUS Serial Speed
R/W
28
Motor Type
R/W
29
MODBUS Device ID
R/W
30
-- spare --
R/W
36
Set/Read Time(Mins,Secs)
R/W
37
Set/Read Time( Hrs, DayOfWeek) R/W
38
Set/Read Time(DayofMonth,
R/W
39
Set/Read Year
R/W
40
Schedule Number
R/W
41
Schedule Day
R/W
42
Start Hour:Min
R/W
43
End Hour:Min
R/W
44
Direction
R/W
45
Speed Reference
R/W
46
Schedule Active
R/W
47
Schedule Status
R
48
-- spare --
R
49
-- spare --
R
8 Bits
Retentive
Signed
Format
Range
Default
x
0,1,2
xxx
1...100
x
0...6
xxx
0..100
0
xxxxx
-400..1100
R
xxx
R
xxx
R
xxx
R
xxx
R
xxx
R
xxxxx
1-500
R
xxxxx
0-65535
S
xxx
-300...300
xxx
0...1000
xxx
0...1000
xx.x
0...150
S
xxx.x
-300...1100
S
xxx.x
-400...1250
S
xxx.x
-300...1350
xxx
0...100
xxx
0-65535
0
0
0
0
R
xxxxx
0-65535
30
x
0...9
5
0..2
0
R
1-247
2
0
R
xx:xx
0-59:0-59
R
xx:xx
0-23:1-7
R
xx:xx
1-31:1-12
R
xxxx
2020-2399
R
x
1-5
1
R
xx
1-127
1
R
xx:xx
0-23:0-59
0x08:01
R
xx:xx
0-23:0-59
0x17:02
R
x
1,2
1
R
xx
0-100
0
R
x
0-1
x
0-1
0
0
SW2 Pin 6
Even Parity: OFF
No Parity:
ON
Description
0=Stop=clear Fault(s); 1=Forward; 2=Reverse; 99=Reset
Percentage of full speed/torque (Blade Size LookUp Table)
1=Comm CRC errors, 2=Drive Faulted, 3=Motor temp warning, 4=IGBT temp warning, 5=Drive Inhibited (Fire Input), 6=Wind Shut Down active
J5 0-10V Output for Optional Light Control (%)
External Temp (°C) (0.1 unit)
Integer code representing fault history
Integer code representing fault history
Integer code representing fault history
Integer code representing fault history
Integer code representing fault history
Operating hours (driving motor)
Motor RPM (0.1 rpm)
Bus Voltage (Volts) (1 units)
RMS Modulated Output Voltage (Volts) (1 Units)
RMS Motor current (Amps) (0.1 units)
Motor Temp (°C) (0.1 units)
Transistor Temp (°C) (0.1 units)
MCU Temp (°C) (0.1 units)
Speed/Torque derate based on overtemp (%)
Number of errors since last power cycle
Seconds; 0: Disables
Baud Rate Setting (SW2: Pin 7 ON)
13,70,170
New Device ID is set after power cycle
High byte Mins; Low Byte Seconds
High byte Hours; Low byte Day of Week
High Byte DayofMonth;
Low Byte Month
Year
Schedule Number
Boolean Value (Bits 6-0)
High byte Hours; Low byte Minutes
High byte Hours; Low byte Minutes
Forward 1; Reverse 2
0-100% Torque
0: Not Active; 1: Active
0: Not Running; 1: Running
SW2 Pins 1-5 Binary Format (Pin 1 = Bit 0)
Address :
1-32
Detail
Resets to 0 after power cycle
Based off an external 10K @ 25C NTC thermistor
At each fault occurance, values are shifted to next register and the current fault is
displayed in Last Fault Code. Values are retained after power cycle.
Incremental Version Count
MAX 65535
Transistor to Heatsink
Thermal regulation (Motor and/or Drive)
0-65535
Any message resets; if a Timeout occurs, Fan will stop (if running)
0
1200 bps
1
2400 bps
2
4800 bps
3
9600 bps
4
19200 bps
5
38400 bps
6
57600 bps
7
115200 bps
0=13; 1 = 70; 2=170
SW2 PIN 8 must be set (on) for this to take effect
Bits 15-8: Minutes
Bits 15-8: Hours; Bits 7-0;DayofWeek (1-7) Mon=1
Bits 15-8: DayofMonth; Bits 7-0: Month
Set this for reading/writing values in registers 41-47
Day 7-1; Bit0 = Mon (1); Bit1=Tues(2); Bit2=Wed(3),etc
From Blade Size Lookup Table
Enable/Disable Schedule
Schedule Running/Not Running

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis