3. Electrical installation
CAUTION
• The UPS system carries life-threatening voltages. All repair and maintenance work
must be carried out by customer service personnel.
• Always connect the earth conductor first.
• Comply with regional legislation and rules on connecting electrical devices.
Table 2: Recommended cable cross sections
Description
Input
Output
Earth conductor
Connection fittings
Cable lug, external max.
Fuse in battery pack
Remove the cover of the terminal strip and connect the cables as shown in the diagrams below:
Figure 1: XANTO 6000 / 10000 terminal strip
Figure 3: XANTO 20000 3/1 terminal strip
XANTO
XANTO
6000
10000
6mm
10mm
2
2
6mm
10mmv
2
6mm
10mmv
2
M5
M5
10mm
10mm
50A
50A
Figure 2: XANTO 10000 3/1 terminal strip
Safety information and quick start guide UPS XANTO
XANTO
XANTO
10000 3/1
20000 3/1
10mm
16mm
2
2
10mm
16mm
2
2
10mm
16mm
2
2
M5
M6
12mm
18mm
100A
100A
Page 11