8.
Set point adjustment
To adjust the contact(s), please remove the transparent cover of the enclosure.
Be careful not to loose the lead-seal when transparent covers is equipped with
this option.
The adjustment of the set point A is done by turning the thumb wheel (3A),
while set point B (2K models only) is set by turning thumb wheel (3B).
The set point(s) be read on the setpoint scale (2).
On devices with one switching contact, the A-contact (left) is adjusted as the
maximum set point (increasing pressure) by factory default.
On devices with two switching contacts, the A-contact (left) is adjusted as the
minimum set point (falling pressure) and the B-contact (right) as the maximum
set point (increasing pressure) by factory default.
The setpoint scale is calibrated at the factory (class 1.0) - no reference pressure
gauges or other aids are required for set point adjustment.
Please note that factory-set and sealed devices should not be adjusted. The
desired function might be affected.
After completing the adjustment, replace the transparent cover and, if neces-
sary, lead-seal the enclosure.
MANOCOMB®-IP65/XD Operating Instructions
actual value indicator (1)
set point scale (2)
set point adjustment A (3a)
set point adjustment B (3b)