DIP switch settings
The actuator is delivered with factory setting as shown in the table
below. All switches are set to "Off", except switch 1.
Off
Off
On
1
Actuator stem retract to
1
close
2
2
Flow: Equal percentage
3
3
Direct action
4
0...10 V input
4
5
Plug: Linear
5
6
Input: 0...10V DC / 2...
10V DC
6
SW1 Operational direction of the valve
Off: The valve is closed when the valve stem is in its highest position.
On: The valve is closed when the valve stem is in its lowest position.
SW2 Desired effective characteristic
Off: Effective equal percentage flow characteristics
On: Effective linear flow characteristics.
See more information under Characteristic curves.
SW3 Reverse/Direct operation
Off: Direct operation. The actuator opens the valve on increasing control
signal.
On: Reverse operation. The actuator closes the valve on increasing
control signal.
SW4 Control signal
Off: 0...10 V DC
On: 2...10 V DC
SW5 Valve flow characteristic
Off: Linear.
On: Equal percentage.
See more information under Characteristic curves.
SW6 Control signal, type
Off: Voltage 0 (2)-10 V
On: Current 0 (4)-20mA
Characteristic curves
The table below shows settings for switch 2 and switch 5. Switch 2 is the
desired effective function you want out of the valve and actuator
combination. Switch 5 is the flow characteristics of the valve itself.
Desired char-
Switch
acteristic
coding
curve
Equal
Switch 2 = Off
percentage
Switch 5 = On
Linear
Switch 2 = On
Switch 5 = On
On
Actuator stem extend to
close
Flow: Linear
Equal
Switch 2 = Off
percentage
Reverse action
Switch 5 = Off
2...10 V input
Plug: Equal percentage
Input: 0...20 mA / 4...20
Linear
Switch 2 = On
mA
Switch 5 = Off
A = Stroke; B = Signal
LED indication
The actuator has two LED lights with indications according to the table
below.
Green LED fixed light
Green LED quick flash
Green LED slow flash (Flash twice +
Off 2 sec.)
Green LED slow flash (Flash twice +
On 1 sec. + Off 1 sec.)
Red LED lights
Characteristic
Characteristic
Effective on
curve for
curve for
valve
valve
actuator
A
A
A
A
A
A
A
A
Actuator moving, under operation
Stroke adaption
0 % position
100 % position
End of SWs fault / more than 2 faults
RVAZ2-24A
Red LED quick flash
One of End SWs fault
Red LED slow flash (Flash once + Off 2
Settings changed during operation
sec.)
Red LED slow flash (Flash twice + Off 2
Auto stroke adapt fault
sec.)
Manual override
To set the actuator to manual override, follow these steps:
1. Remove the manual override rubber seal with a screwdriver to have
access to the Allen key hole.
2. Use the 4 mm Allen key to turn the screw.
1
2
– Turn the Allen key clockwise to extend the actuator stem. This
closes the valve if the valve itself is closing when valve stem is
pushed into the valve.
– Turn the Allen key counterclockwise to retract the stem. This opens
the valve if the valve itself is closing when valve stem is pushed into
the valve.
Figure 3 Left: Valve is open when the valve stem is extended. Right: Valve is closed
when the valve stem is pushed into the valve.
N N o o t t e e ! ! If the valve opens when the valve stem is pushed in, the function is
the opposite.