7XT3300-0*A00
Technical Data
Auxiliary Voltages
Voltage supply via extended range power supply unit
DC Voltage
Nominal auxiliary DC voltage
Permissible DC voltage range
AC Voltage (50 Hz to 60)
Nominal auxiliary AC voltage, 3-phase
Nominal auxiliary AC voltage, single-phase
Permissible DC voltage range
Power consumption on 8 impedance
(8 = series resistance of the 7XT34 with 20 Hz)
Bridging time for failure auxiliary voltage
(DC 110 V)/short-circuit
20-Hz Output Voltage
Terminal points 11 and 12
Output voltage
Power output, permanently
Efficiency with R
= 8
L
C53000-B1174-C129-8
NOTE
The output of 7XT33 is not resistant to short-circuits. In the case of a
short-circuit the internal fusible cut-out insert interrupts the electrical
circuit.
DC 110 V to DC 220 V
DC 88 V to DC 250 V
3 x AC 100 V to AC 120 V
AC 100 V to AC 120 V
AC 88 V to AC 230 V
100 VA
50 ms with rated load (at connected
bandpass 7XT34)
26 V ± 10 %, rectangular, 20 Hz ± 0.1 Hz
100 VA over all input voltage ranges
approx. 76 %
English
41