Herunterladen Inhalt Inhalt Diese Seite drucken

Application; Features / Benefits; Standard Version - Camille Bauer SINEAX C 402-1 Betriebsanleitung

Grenzwertmelder
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Operating Instructions
Alarm unit SINEAX C 402-1
for DC currents or DC voltages
Contents
1. Application ................................................................ 17
2. Features / Benefits .................................................... 17
3. Standard version ....................................................... 17
4. Technical data ........................................................... 18
5. Coding of the variants ............................................... 19
6. Data on explosion protection .................................... 20
7. Configuration ............................................................. 21
8. Electrical connections ............................................... 22
9. Exchanging frontplate ............................................... 22
10. Withdrawing and inserting the device ....................... 22
11. Mounting ................................................................... 23
12. Dimensional drawings ............................................... 23
13. Standard accessories ................................................ 23
14. Declaration of conformity .......................................... 24

1. Application

The alarm unit SINEAX C402 (Fig. 1) is normally applied to
monitor the limits of both current and voltage measurements.
The status of the device is signalled remotely by a relay and
locally by LED's. The electrical insulation between input,
output relay contacts and the power supply conforms to
IEC 1010. The value detected by the alarm unit is set on a
potentiometer and measured at test sockets on the front
of the unit.
The alarm unit fulfils all the important requirements and
regulations concerning electromagnetic compatibility EMC
and Safety (IEC 1010 resp. EN 61 010). It was developed
and is manufactured and tested in strict accordance with the
quality assurance standard ISO 9001/EN 29 001.
Production QA is also certified according to guideline
94/9/EG.

3. Standard version

The following alarm unit in housing S17 is available as standard version. Measuring input set to 0 ... 20 mA resp. 0 ... 10 V
- acc. to external connection - (plug-in jumper J1 in position B2). Any of the standard ranges simply selected by positioning
plug-in jumpers J1. Quoting the order No. is sufficient when ordering:
Table 1: Instrument in standard (non-Ex) version
Standard input signals
0 ... 20 mA / 0 ... 10 V
4 ... 20 mA / 2 ... 10 V
± 20 mA / ± 10 V
Please complete the Order Code 402-1... ... .. according to table 3.
Basic configuration see Section "4. Technical data".
All manuals and user guides at all-guides.com
Contact outputs A1 / A2
2 relay outputs
with
1 changeover contact each
II (1) G
0102
Fig. 1. SINEAX C 402-1 with 2 relay outputs with 1 changeover
contact each, in housing S17 clipped onto a top-hat rail.

2. Features / Benefits

● With 2 alarm circuits
● Analogous trip point adjusted by 12-turn potentiometer, adjusted
trip point measurable on test sockets, 0...1 V
● Sense of relay action and associated LED's switchable by
jumpers
● Electrical insulation between measuring input, contact outputs
and power supply / Fulfils EN 61 010
● Non-standard user-specific ranges available
● AC/DC power supply / Universal
Available in type of protection "Intrinsic safety" [EEx ia] IIC (see
Section 6: Data on explosion protection)
Power supply
85 ... 230 V DC/AC
0...100%
Order Code
Order No.
402 - 1202
128 654
17

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis