I I Monitoring excess flow
With this function the position of the display window within the
detection range can be defined: Shift the LED for the maximum dis-
play value to position 8, 7, 6 or 5. In the case of maximum flow all
LEDs from 0 up to this LED are lit. The LEDs above the range signal
excess flow. If the switch point is above this range, the unit switches
in the case of excess flow.
M
S
1
2x
M
S
2
5 s
M
S
3
M
S
4
Please note:
The display value is reset (to LED 9) after each maximum flow rate adjustment
(HI-Teach.
All manuals and user guides at all-guides.com
Ensure you are in run mode flow.
LO
LO
LO
LO
Press the Mode/Enter button
HI
twice. The current setting is indi-
cated (green LED).
HI
Press the Learn/Set button for 5 s
(until LED flashes).
Press the Learn/Set button
HI
several times until the requested
LED flashes (LED 8, 7, 6 or 5).
Each time the button is pressed
the LED moves back by one position.
When it is lower than LED 5 the
cycle starts again at LED 9.
Press the Mode/Enter button
HI
briefly (acknowledgement).
The indication goes off briefly.
The unit stores the new setting
and passes into the run mode flow.