IFM Electronic Efector 300 SI1007 Bedienungsanleitung Seite 28

Strömungswächter

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

I I Setting the output function for S2
• Ensure you are in run mode temperature.
• Press the Mode/Enter button twice.
• Press the Learn/Set button for 5 s, release when LED flashes.
• Press the Learn/Set button several times to shift the LED for the
requested output function.
Logic
For use as N.O. function S2 is
function
switched when
0
1
2
3
4
5
6
7
8
9
• Press the Mode/Enter button briefly.
I I Reset to factory settings
• Ensure you are in run mode flow.
• Press the Learn/Set button for >15...<20 s.
I I The following applies to all setting procedures:
• The internal sensing, processing and output functions of the unit
continue as if in Run mode with the original parameter values
unless a new value is confirmed.
• If no button is pressed for 15s during the setting procedure, the unit
returns to the operating mode with the parameter values unchanged.
• If adjustment has not been possible, all the red LEDs flash. The unit
returns to the operating mode with the parameter values
unchanged.
I I Locking / Unlocking:
The unit can be electronically locked to prevent unwanted adjustment
of the set parameters: Press both setting buttons for 10 s (the unit
must be in Run mode). Indication goes out briefly (acknowledgement
of locking / unlocking).
28
All manuals and user guides at all-guides.com
temperature ≥ SP
flow ≥ SP
and temperature ≥ SP
Flow
flow ≥ SP
and temperature < SP
Flow
flow < SP
Flow
flow < SP
and temperature < SP
Flow
flow ≥ SP
Flow
flow ≥ SP
Flow
flow < SP
Flow
flow < SP
Flow
temperature < SP
For use as N.C. function S2 is
not switched when
Temp
and temperature ≥ SP
or temperature ≥ SP
or temperature < SP
or temperature ≥ SP
or temperature < SP
Temp
Temp
Temp
Temp
Temp
Temp
Temp
Temp
Temp