4. Wire supplied connector plug.
5. Attach touchscreen operating unit (steps ① to
③)
6. Plug connector plug into operating unit and
screw in.
7. Push the operating unit onto the mounting
plate and snap it into place.
8. Check the function of the touchscreen operat-
ing unit.
Connecting cables in ventilation unit
6 Installation of RLS T2 WS
9. Remove front cover(s) → Installation instruc-
tions for ventilation unit.
10.Lift electronic slide-in module and pull out of
the electronics compartment. Hang slide-in
module in fitting studs (if present).
NOTICE If the connection cables are too
short, the electronic slide-in module cannot
be fully pulled out/fitted.
Ensure connection cables of a sufficient length
inside the ventilation unit.
NOTICE Danger of short-circuits/damage to
unit should water enter the electronics com-
partment.
Ensure correct, tight line feed through the cable
feedthrough.
11.Correctly push through cable feedthrough.
12.Guide connection cable through cable feed-
through into ventilation unit.
13.Check for leaks and remedy any found.
Only guide connection cable individually
through the cable feedthrough. Feedthroughs
which are not needed must remain sealed.
14.Wire cables on control circuit board A2, ter-
minal block X11 (RS 485) according to wiring
diagram of ventilation unit.