Herunterladen Inhalt Inhalt Diese Seite drucken

fisair DFLEX Serie Bedienungsanleitung Seite 41

Vorschau ausblenden Andere Handbücher für DFLEX Serie:
Inhaltsverzeichnis

Werbung

DFLEX-2100 PARAMETERS
Code
Page
67
[Auto Set Function]
97
[Accel. time 1]
97
96
[Decel. time 1]
168
96
[Maximum
168
frequency]
96
[Freq upper limit]
167
96
[Freq lower limit]
167
74
[Nominal freq,
167
motor]
74
[Nominal voltage,
166
motor]
74
[Thermal prot motor]
104
[Selection Ll F]
[Function 1 RY
124
Relay]
[Function 1 FL
125
Relay]
119
[RY Delay]
120
[FL Delay Relay]
123
[Auto/man ref speed]
121
[Point 2 freq VIA]
74
[I Nominal Motor]
74
[Nom Motor Speed]
73
[I Motor Limit]
Name
Unit
-
s
-
s
-
Hz
-
Hz
-
Hz
-
Hz
-
models
V
models
% / A
-
0-61. 254,
-
0-61, 254,
-
s
s
-
Hz
A
rpm
%/A
Handbuch zur bedienung und steuerung baureihe DFLEX | 41
Setting range / Function
0
[Factory parameter]
1
[Run permissive]
2
[3-wire]
3
[+/- Speed]
4
[4-20mA ref. speed]
0.0 - 3200
0.0 - 3200
30.0-400.0
0.5-
[Max.Freq.]
(F H)
0.0 -
[Freq upper limit]
25.0 - 200.00
230V
50 - 330
460V
50 - 660
-
10-100% of nominal inverter output current
0-72
See table on page 200
See table on page 200
255
See table on page 200
255
-
0,0-60,0 s
-
0,0-60,0 s
0
[Enabled]
1
[Disabled]
0,0 - 200,0
-
0.1 - 200.0
-
100- 15000
-
10-110%
Factory
setting
0
Depends on
the model
Depends on
the model
80.0
50.0
(U L)
0.0
50.0
230
400
100%
2
4
11
0,0
0,0
0
50.0
Depends on
the model
Depends on
the model
110%
User
setting
0
60
60
59
58
0
According to
pate
According to
plate
According to
inverter
plate
2
14
22
1
3
0
58
According to
motor plate
According to
motor plate
According to
motor plate

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis